SIZE | ||||
No. of Zones | Model No. | Part No. | Size (mm) (W x D x H) | |
Indoor | Outdoor | |||
2 | PE-GRP 200i / PE-GRP 200s | FAP-02ZCP-N | 430 x 370 x 170 | 430 x 380 x 170 |
4 | PE-GRP 400i PE-GRP 400s | FAP-04ZCP-N | 550 x 390 x 170 | 550 x 400 x 170 |
TECHNICAL DATA | ||||
Power Supply Input | 240V AC 50Hz/60Hz | |||
Operating System | 24V DC | |||
Operating Battery | 18-27.6V DC | |||
Battery Cut Off | 18V | |||
Intelligent Charger (S1) | 0.67A – 1.3A @ 30% | |||
Intelligent Charger (S5) | 1.2A – 1.8A @ 100% | |||
End of Line | 8K2 Ohms | |||
Auxiliary Output | 24V, 2 Amp | |||
Alarm Signal | N/O Contact | |||
Gas Discharged Signal | N/O Contact | |||
STANDBY MODE | ||||
Master | 75mA | |||
Per zone (with Detectors) | 5mA | |||
Flashing Lights (Green LED) | 75mA | |||
ALARM MODE | ||||
Master | 140mA | |||
Per Trigger Zone | 70mA | |||
Output Devices | 200mA | |||
Flashing Lights (Red LED) | 75mA | |||
Per Bell | 30mA |
*Applicable for Carbon Dioxide Extinguishing System