FEATURES
• USB configurable
• DIN rail mounting
• 4-ways galvanically isolated
• Universal power supply AC/DC
• Programmable alarm contact
• RS485 Modbus & Analog Output
• DATALOGGING via USB with USB thumb drive
• Download storage data on excel importable files
• RTC Real Time Clock integrated
VOLTAGE:
Up to 10 Vdc programmable, input impedence 100KOhm, 1mV resolution.
CURRENT:
Up to 20 mA programmable, input impedence 20 Ohm, max resolution 2μA.
TEMPERATURE:
RTD : Pt100, Pt500, Pt1000, Ni100. 2,3 or 4 wire measure, automatic detection of cable interruption.
TC Tipe : J, K, R, S, T, B, E, N; automatic detection of cable interruption (-10mV to 70mV).
POTENTIOMETER:
From 1000 Ohm to 10K ohm.
FREQUENCY:
From 0,001 Hz to 9,99KHz, mechanical contact, npn 2 and 3 wires, pnp 3 wires with supply of 24 Vdc, namur, photoelectric, Hall sensor, variable reluctance, pulse 24 V, TTL.
CURRENT:
0...20mA programmable, max load resistence 600 ohm.
VOLTAGE:
0...10V programmable, min load resistence 2k ohm.
CONTACT ALARM:
5A 230Vac SPDT relay fully programmable by FACILE QA-OMNI.
RS485 MODBUS:
Bus connection on the base of module by adapter (option) or on terminals. Dip-switch for setting address and baudrate.
QA-OMNI SPECIFICATIONS:
POWER SUPPLY | 10..40 Vdc, 20-28 Vac, 50-60 Hz |
---|---|
RETRASMISSION OUTPUT | On isolated analog output, Voltage and Current (impressed) programmable; Active or Passive supply output. Sensor power supply 13 Vdc, 30mA max |
ABSORPTION | Maximum 2,5 VA |
PROTECTION INDEX | IP20 |
ACCURACY | 0,1% F.S. |
RESOLUTION | 16 bit (15 + sign for TC) |
REJECTION | 50-60 Hz |
THERMAL STABILITY AT 25°C | <100 ppm/°C |
WORKING TEMPERATURE | -15...+65°C |
STORAGE TEMPERATURE | -40°C... +85°C |
ISOLATION | Input, analog and digital output, serial output RS485 and USB port, Power supply, are 4-way galvanically isolated at 1,5kV |
HUMIDITY | 10...90% not condensing |
ALTITUDE | Up to 2000 m s.l.m |
MOUNTING | DIN rail mounting with removable terminals, RS485 bus and Supply connection ready on the base of module (connector not included, on request) |
CONNECTIONS | Removable terminals 5,08mm |
CE STANDARDS | EN61000-6-4/2006 + A1 2011; EN64000-6-2/2005; EN61010-1/2010 |
DIMENSIONS | 17,5 x 100 x 112 mm (terminals excluded) |
DATA LOGGER | Non-volating memory. Log on USB OnTheGo port by Pen Drive stick memory. The software FACILE QA-OMNI (free of charge) allow you to configure Log, all conversion parameters, set contact alarm, set Modbus address. RTC Real Time Clock integrated. |
CONFIGURATION | By free software FACILE QA-VI to configure all of the conversion parameters like span, zero, alarm contact and log via USB port or via RS485. Dip-switch for setting modbus address and baudrate |