TruVu™ MPC Processor TV-MPCXP

TruVu™ MPC Processor TV-MPCXP

分类: Carrier 当前有货
欲了解更多详情,请游览我们的官方网站 unitedfaith.com.my

详情

The Carrier® TruVu™ MPC Processor provides multipurpose monitoring and control for a variety of HVAC system applications. Flexible and versatile, it supports multiple I/O configurations for accomplishing both common and custom HVAC control strategies.

The TruVu MPC Processor features built-in routing and integration capabilities, along with support for up to nine TruVu MPC I/O expansion modules and a total of 180 input/output points.
 

Application Features

Hardware Features

BACnet Features

System Benefits


BACnet Support Conforms to the BACnet Building Controller (B-BC), BACnet Router (B-RTR), and BACnet BBMD (B-BBMD) device profiles as defined in BACnet standard135-2001 Annex L 2012
Communication Ports Gig-E: 10/100/1000 BaseT Ethernet port for BACnet/IP and/or BACnet/Ethernet and/or Modbus Ports TCP/IP communication
S1 ARC/MSTP: High-speed EIA-485 port with End of Net switch for connecting one of the following:
• BACnet ARCnet network at 156 kbps
• BACnet MS/TP network at 9.6, 19.2, 38.4, 57.6, 76.8, or 115.2 kbps
• Modbus RTU at 9.6, 19.2, 38.4, 57.6, 76.8 or 115.2 kbps
S2 MSTP: Electrically isolated EIA-485 port with End of Net switch for connecting one of the following:
• BACnet MS/TP network at 9.6, 19.2, 38.4, 57.6, , 76.8, or 115.2 kbps
• Modbus RTU at 9.6, 19.2, 38.4, 57.6, 76.8 or 115.2 kbps
Service: 10/100 Base T Ethernet port for system start-up and troubleshooting
IO Bus port: Provides communication for wired TruVu MPC I/O expanders that are powered by external power supplies.
IO Bus edge connector: 6-pin connector that provides communication and power to a directly-connected TruVu MPC I/O expander
Third Party Integration Supports up to 1,500 third-party BACnet points and 200 Modbus points (memory dependent).
Physical Fire-retardant plastic ABS, UL94-5VA
I/O Expanders Supports up to 9 TruVu™ MPC I/O expanders and/or 6 MPC Open XPIO expanders (max 9 total)
Protection Two fast acting, 5mm x 20mm glass fuses:
• A 2A fuse for the TV-MPCXP’s power
• A 4A fuse for the I/O bus edge connector
Compliance United States of America: FCC compliant to Title CFR47, Chapter 1, Subchapter A, Part 15, Subpart B, Class A; UL listed to UL916, PAZX, Energy Management Equipment
Canada: Industry Canada Compliant, ICES-003, Class A; cUL listed UL 916, PAZX and Energy Management Equipment
Europe: EN50491-5-2:2009; Part 5-2: EMC requirements for HBES/BACS used in residential, commercial and light industry environment EN50491-3:2009, Part 3: Electrical safety requirements for Home and Building Electronic Systems (HBES) and Building Automation and Control Systems (BACS) Low Voltage Directive: 2014/35/EU RoHS Compliant: 2011/65/EU
Australia and New Zealand: C-Tick Mark, AS/NZS 61000-6-3
Real Time Clock Real-time clock keeps track of time in the event of a power failure for up to 3 days.
Environmental Operating Range -40 to 158ºF (-40 to 70ºC) 10 to 95% RH, non-condensing