Item |
Data |
Inserts |
MatchingD24B Hoods&Housings |
APPROVAL |
UL.CSA.VDE.CE.CQC |
Test standard |
DIN EN61 984 / UL1977 |
Poles |
4/8P+PE |
The need for additional or dering crimp contacts) |
否 |
|
No |
EN61984 Test data |
/ |
Rated voltage [V] |
400/400 |
Rated current [A] |
80/16 |
pollution degree |
3 |
Rated impulse voltage [KV] |
6-Jun |
Insulation resistance |
≥1010Ω |
UL/CSARated current [V] |
600/600 |
Material |
Polycarbonate |
Inflammability class(UL94) |
V-0 |
Ambient temperature [℃] |
-40~+125 |
Mechanical working life(mating cycles) |
≥500 |
Contacts |
|
Material |
Copper alloy |
Surface |
Hard-silver plated |
Contact resistance |
Power area ≤0.3mΩ |
|
Signal area ≤1mΩ |
Terminal |
Screw terminal |
Power area Screw terminal tightening |
1.5 2.5 4 6 10 16( mm²) |
|
1.2 2 3 3 3 3 [N·m] |
Signal area Screw terminal tightening |
0.5 [N·m] |
Power area connection capacity(solid/stranded) |
1.5-16mm² (AWG16-6) |
Signal area connection capacity(solid/stranded) |
0.5-2.5mm² (AWG20-14) |
Screw |
M6/M3, (Steel,Ni plated ) |
Wire connecting |
|
Recommended stripping length/Power area14mm/Signal area 7.5mm |
For solid wire, stripping wire to the appointed length, then tightening with rated torque. |
For stranded wire: stripping wire to the appointed length, mating with corresponding type of ferrule, then tightening with rated torque. |
Tightening process should be steady, can’t use explosive force. |