KFD2-CRG2-Ex1.D

Category: Signal Converter & Signal Isolator Available
For more information, visit our official website at ecinstruments.net

Description

Transmitter Power Supply KFD2-CRG2-Ex1.D

 

General specifications
Signal type Analog input
Functional safety related parameters
Safety Integrity Level (SIL) SIL 2
Supply
Connection Power Rail or terminals 23+, 24-
Rated voltage 20 ... 30 V DC
Rated current approx. 130 mA
Power dissipation 2 W
Power consumption 2.5 W
Interface
Programming interface programming socket
Input
Connection side field side
Connection terminals 1, 2, 3
Input I  
  Input signal 0/4 ... 20 mA
  Available voltage ≥ 15 V at 20 mA
  Open circuit voltage/short-circuit current 24 V / 33 mA
  Input resistance 45 Ω (terminals 2, 3)
  Line fault detection breakage I < 0.2 mA; short-circuit I > 22 mA
Output
Connection side control side
Connection output I: terminals 10, 11, 12
output II: terminals 16, 17, 18
output III: terminals 8+, 7-
Output signal 0 ... 20 mA or 4 ... 20 mA
Output I, II signal, relay
  Contact loading 253 V AC / 2 A / cos φ ≥ 0.7 ; 40 V DC / 2 A
  Mechanical life 5 x 107 switching cycles
Output III Signal, analog
  Current range 0 ... 20 mA or 4 ... 20 mA
  Open loop voltage max. 24 V DC
  Load max. 650 Ω
  Fault signal downscale I ≤ 3.6 mA, upscale I ≥ 21 mA (acc. NAMUR NE43)
Energized/De-energized delay 0 ... 250 s , adjustable
Transfer characteristics
Input I  
  Accuracy < 30 µA
  Influence of ambient temperature 0.003 %/K (30 ppm)
Output I, II  
  Response delay ≤ 200 ms at bounce from 0 ... 20 mA
Output III  
  Resolution ≤ 10 µA
  Accuracy < 20 µA
  Influence of ambient temperature 0.005 %/K (50 ppm)
  Reaction time < 650 ms at bounce from 0 ... 20 mA at the input, 90 % of output full-scale value
Galvanic isolation
Input/Other circuits reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output I, II/other circuits reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Mutual output I, II, III reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output III/power supply and collective error functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Interface/power supply and collective error functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Indicators/settings
Display elements LEDs , display
Control elements Control panel
Configuration via operating buttons
via PACTware
Labeling space for labeling at the front
Directive conformity
Electromagnetic compatibility  
  Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Low voltage  
  Directive 2014/35/EU EN 61010-1:2010
Conformity
Electromagnetic compatibility NE 21:2006
Degree of protection IEC 60529:2001
Ambient conditions
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protection IP20
Connection screw terminals
Mass 300 g
Dimensions 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) (W x H x D) , housing type C2
  Height 119 mm
  Width 40 mm
  Depth 115 mm
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-type examination certificate TÜV 01 ATEX 1701
  Marking Ex-Hexagon II (1)G [Ex ia Ga] IIC
Ex-Hexagon II (1)D [Ex ia Da] IIIC
Ex-Hexagon I (M1) [Ex ia Ma] I
  Input Ex ia
Supply  
  Maximum safe voltage 40 V DC (Attention! The rated voltage can be lower.)
Equipment terminals 1+, 3-
  Voltage 25.8 V
  Current 93 mA
  Power 0.603 W
Equipment terminals 2-, 3
  Voltage < 30 V
  Current 115 mA
  Voltage 5 V
  Current 0.3 mA
  Power 0.3 mW
Equipment terminals 1+, 2 / 3-
  Voltage 25.8 V
  Current 112 mA
  Power 720 mW
Output I, II terminals 10, 11, 12; 16, 17, 18 non-intrinsically safe
  Maximum safe voltage 253 V AC / 40 V DC (Attention! Um is no rated voltage.)
  Contact loading 253 V AC/2 A/cos φ > 0.7; 40 V DC/2 A resistive load
Output III terminals 8+, 7- non-intrinsically safe
  Maximum safe voltage Um 40 V (Attention! The rated voltage can be lower.)
Interface RS 232
  Maximum safe voltage 40 V (Attention! The rated voltage can be lower.) , RS 232
Certificate TÜV 02 ATEX 1885 X
  Marking Ex-Hexagon II 3G Ex nA nC IIC T4
Output I, II  
  Contact loading 50 V AC/2 A/cos φ > 0.7; 40 V DC/2 A resistive load
Galvanic isolation  
  Input/Other circuits safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity  
  Directive 2014/34/EU EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
FM approval  
  Control drawing 16-554FM-12 (cFMus)
UL approval E223772
IECEx approval  
  IECEx certificate IECEx TUN 09.0007
IECEx TSA 18.0007X
  IECEx marking [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
Ex ec nC IIC T4 Gc
General information
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

More detail about EC Instruments & Engineering Sdn Bhd
EC Instruments & Engineering Sdn Bhd
EC Instruments & Engineering Sdn Bhd Electrical Instruments Johor Bahru (JB), Electronic Components Supplier Malaysia, Sensors Supply Singapore, Perak ~ EC Instruments & Engineering Sdn Bhd
Contact Us flagMalaysia