Spring-loaded governors, are designed and built according UNI EN 88 class A - group 2 specifications, can be used for all the types of natural gas LPG or not corrosive gases . These regulators are widely used in supply lines for mixed and combinated burners and in the piped distribution of methane gas and LPG in both industrial and non-industrial applications.
Spring-loaded/ governors are self-acting type with balanced obturator and double safety diaphragm. The double diaphragm allow to use the device within the cabinet, without connecting an external pipe venting. (Point 3.3.2 of UNI EN 88 regulation). All regulators have internal sensing line and inlet/outlet pressure test point
0497
Pmax inlet max – 500 mbar
Setting outlet 10 – 300 mbar – Standard spring supplied 10 – 27 mbar –
Other spring on request
Filtering ≤ 50μm – Viledon cartridge Inlet- Outlet Thread gas 2'' - ISO 228
Connection DN50 - Sliding Aluminium flange PN10
Test point Inlet / outlet on request – Test point 1/8'' NPT
Working Temperature - 20 °C – + 60 °C
Use Not aggressive gases of three families – Natural Gas – LPG – Town Gas
Approval UNI EN 88-1:2011 - PED
Complete Body Die – Cast Aluminium Gd – AlSi12Cu – EN AB 46100
Diaphragms NBR 60Sh – DvGW EN 549
Plastic components Yellow POM / Pa 66 + 25% Gf
Color: White Range: 5 - 14 mbar
Color: Yellow Range: 6 - 22 mbar
Color: Neutral Range: 10 - 27 mbar
Color: Red Range: 28 - 70 mbar
Color: Black Range: 60 - 130 mbar
Color: Blue Range: 120 - 300 mbar
If you want test point in and out pls add code TPIO at the end of the code.