Product Integrated Controller

Integrated controller for fan coil units capable of stand-alone operation or integrated with Carrier’s or any Building Automation System using BACnet®, Modbus® or Lonworks® protocol

Carrier’s Fan Coil Open Controller is an integrated component of a Carrier fan coil unit. The Fan Coil Open controller continuously monitors and regulates fan coil operation with reliability and precision. This advanced controller features a sophisticated, factory-engineered control program that provides optimum performance and energy efficiency. The Fan Coil Open controller also features plug-and-play connectivity to the Carrier i-Vu Building Automation System.

For added flexibility, the Fan Coil Open controller is capable of stand-alone operation, or it can be integrated with any Building Automation System utilizing the BACnet protocol.


carrier-bacnet-international-member
carrier-bacnet-testing-laboratories

 

Application Features

Hardware Features

System Benefits


Specifications

BACNet Support Advanced application controller (B-AAC), as defined in BACNet 135-2001 Annex L
Communication Ports Network port: EIA-485 port for BACnet MS/TP communications (baud rates is DIP switch selectable)
Comm Option Port: For connecting a LON Option Card (future)
Local Access port: For system start-up and troubleshooting (115.2 kbps)
Rnet port: For connecting Carrier communicating room sensors and Carrier's touchscreen user interface
Inputs 2 binary inputs: Remote Occupancy Contact/Fan Status and Condensate Overflow
4 analog inputs: RH/CO2 (0-5VDC), SAT (10k thermistor), RAT/T55 (10k thermistor) and Changeover Switch (dry contact)/Changeover Sensor (10k thermistor). AIs have 10 bit A/D resolution.
Outputs 5 binary outputs: High Speed Fan, Medium Speed Fan, Low Speed Fan, Two-Pipe Valve/Heating Valve/Electric Heat Stage 1, and Cooling Valve/Electric Heat Stage 1 with Type 5 Heat and 2-Pipe. Relay contacts rated at 1 A max @ 24 VAC/VDC, configured normally open.
3 analog outputs: OA Damper, 2-Pipe/Heating Valve and Cooling Valve. AOs rated at 0-10VDC, 5mA max with 8 bit A/D resolution using filtered PWM.
Protection Incoming power and network connections are protected by non-replaceable internal solidstate polyswitches that reset themselves when the condition that causes a fault returns to normal. The power, network, input, and output connections are also protected against voltage transient and surge events..
Real Time Clock Battery-backed real time clock keeps track of time in event of power failure
Battery 10-year Lithium CR2032 battery provides a minimum of 10,000 hours of trend data & time retention during power outages.
Status Indicators LED status indicators for communications, run status, error, power, and all digital outputs.
Controller Addressing Rotary DIP switches set BACnet MS/TP MAC address of controller.
Listed By UL-916 (PAZX), cUL-916 (PAZX7), FCC Part 15-Subpart B-Class A, CE EN50082-1997
Environmental Operating Range Operating: 0° to 140°F (-18° to 54°C), 10-90% relative humidity, non-condensing
Storage: -24°F to 140°F (-30° to 60°C), 10-90% relative humidity, non-condensing
Power Requirements 24VAC +/- 10%, 50-60Hz
18VA power consumption
26VDC (25V min, 30V max)
Single Class 2 source only, 100VA or less
 