WeatherMaster® 50HCQ rooftop units were designed to be easy to install, maintain, and operate, with customer-requested features including a gage port, centralized control center, plug-and-play accessory board, ''no-strip screw'' collars, and handled access panels. Units are field-convertible to horizontal airflow without special adapter curbs or kits, making it easy for the installer to adjust to unexpected jobsite complications. Units are pre-wired and pre-charged with environmentally sound Puron (R-410A) refrigerant and are factory tested.
Heat Pump with Puron® (R-410A) Refrigerant
3 to 10 Nominal Tons
Nominal Cooling Ton Size | Cooling Stages | AHRI Efficiency (SEER) EER | Dimensions (in) LxWxH | At 47°F | At 17°F | Unit Weight (lbs) | ||
---|---|---|---|---|---|---|---|---|
Heating Capacity (Btuh) | (HSPF) COP | Heating Capacity (Btuh) | (HSPF) COP | |||||
3 | 1 | (15.6) | 74 x 47 x 33 | 34000 | (8.00) | 18400 | (N/A) | 495 |
4 | 1 | (15.8) | 74 x 47 x 41 | 46000 | (8.10) | 23800 | (N/A) | 580 |
5 | 1 | (15.0) | 74 x 47 x 41 | 55000 | (8.20) | 28600 | (N/A) | 610 |
6 | 1 | 12.0 | 88 x 59 x 41 | 70000 | 3.40 | 39000 | 2.40 | 710 |
7.5 | 2 | 12.1 | 88 x 59 x 49 | 84600 | 3.50 | 47000 | 2.40 | 875 |
8.5 | 2 | 12.0 | 88 x 59 x 49 | 100000 | 3.40 | 56000 | 2.26 | 1020 |
10 | 2 | 12.3 | 116 x 63 x 57 | 116000 | 3.50 | 65000 | 2.40 | 1390 |