50HC WeatherMaster® rooftop unit were designed by customers for customers. With a gauge plug, centralized control center, plug & play accessory board, ''no-strip screw'' collars, and handled access panels, we’ve made the unit easy to install, easy to maintain, and easy to use. Units are pre-wired and pre-charged with environmentally sound Puron® (R-410A) refrigerant at the factory. The units are factory tested in cooling mode.
Electric Cooling with Puron® (R-410A) Refrigerant
3 to 25 Nominal Tons
Nominal Cooling Ton Size | Cooling Stages | AHRI Efficiency (SEER) EER | Dimensions (in) LxWxH | Electric Heat Nominal Kilowatt Range | Approx. Unit Weight (lbs) |
---|---|---|---|---|---|
3 | 1 | (15.0) | 74 x 47 x 33 | 4.0 to 16.0 | 458 |
4 | 1 | (15.6) | 74 x 47 x 41 | 4.4 to 23.0 | 545 |
5 | 1 | (15.2) | 74 x 47 x 41 | 6.5 to 26.5 | 550 |
6 | 1 | 12.2 | 88 x 59 x 41 | 6.0 to 26.5 | 715 |
7.5 | 2 | 12.2 | 88 x 59 x 49 | 10.0 to 42.4 | 860 |
8.5 | 2 | 12.2 | 88 x 59 x 49 | 10.4 to 42.4 | 860 |
10 | 2 | 12.0 | 88 x 59 x 49 | 10.0 to 51.0 | 865 |
10 | 2 | 11.7 | 88 x 59 x 49 | 10.0 to 51.0 | 865 |
12.5 | 2 | 12.4 | 116 x 63 x 57 | 15.0 to 51.0 | 1075 |
15 | 2 | 12.2 | 128 x 87 x 49 | 25.0 to 75.0 | 1093 |
17.5 | 2 | 12.2 | 141 x 87 x 49 | 25.0 to 75.0 | 1793 |
20 | 2 | 12.2 | 141 x 87 x 57 | 25.0 to 75.0 | 2148 |
25 | 2 | 11.4 | 158 x 87 x 57 | 25.0 to 75.0 | 2193 |