详情
MGS-450 Gas Detector
Used for detection of refrigerants, toxic and combustible gases
Bacharach’s MGS-450 Gas Detector makes compliance with refrigeration safety codes (ASHRAE 15, EN 378, CSA-B52) simple and effective, saving time and money on equipment and installation.
- Optional IP41 or IP66-rated enclosures protect from dust and water ingress
- Plug-and-play pre-calibrated sensor modules allow for quick, simple sensor replacement
- Temperature-compensated measurements mitigate false alarms and optimize accuracy in refrigeration applications (suitable for use in cold rooms and freezers down to -40°C)
- Configurable analog output (4-20mA, 0-5V, 0-10V, 1-5V or 2-10V) and Modbus communications for integration with Bacharach’s MGS-408 controller or third-party BMS / BAS control systems
- Three user-configurable relays (fault, low and high alarm) may be used to activate external beacons / sounders, ventilation or other countermeasures
- Integrated audible / visual alarms for refrigeration safety compliance – no additional hardware required
- MGS-400 mobile app (available for Android and iOS) allows users to interface via Bluetooth® with gas detector for easy commissioning and maintenance without specialty tools or training
SPECIFICATIONS
Accuracy : SC - < -10%/+15% of Full-Scale; IR, Cat, EC - < ±5% of Full-Scale
Alarm : Integrated Audible / Visual Alarm
Altitude : 0 to 6,560 ft (2,000 m)
Ambient Temperature : -40 to 122°F (-40 to +50°C)
Analog Communication : 4 to 20 mA, 0 to 5 V, 0 to 10 V, 1 to 5 V, 2 to 10 V
Approvals / Standards : CE, UL / CSA / IEC EN 61010-1
Buzzer Volume : 80 dB @ 10 cm
Country of Origin : United States
Digital Communications : Modbus RTU via RS 485
Enclosure Rating : IP41
Humidity : 5 to 90% RH, non-condensing
Measuring Range : Sensor Dependent (See Datasheet)
Operating Voltage : 24 VDC
Power : 19.5 to 28.5 VDC or 24 VAC ±20%; 4W
Product Dimensions (L×W×H) : IP41: 6.5” × 6.5” × 3.0” (165 × 165 × 77 mm)
Product Weight : 1lb, 1oz (480 g)
Relay Rating: 2 Alarm relays, 1 Fault relay SPDT
Resolution : Sensor & Gas Concentration Dependent (See Datasheet)
Sensitivity/Minimum Detection Limit : Sensor Dependent (See Datasheet)
Sensor Channels : 1
Sensor Type : Sensor Dependent (See Datasheet)
User Interface : MGS 400 Series App
Warranty :1 Year
Wiring : 1 A @ 30 VDC
APPROVALS
Approvals subject to change without notice and may differ based on configuration, part number and/or country. Contact Customer Service or check approval label on product for specific approval information.
EU (DoC)
EU (DoC) A1 Refrigerants and CO2