P+F KFD2-SCD2-Ex2.LK SMART Current Driver

P+F KFD2-SCD2-Ex2.LK SMART Current Driver

分类: Signal Converter & Signal Isolator 当前有货
欲了解更多详情,请游览我们的官方网站 ecinstruments.net

详情

SMART Current Driver KFD2-SCD2-Ex2.LK

< 2-channel isolated barrier
< 24 V DC supply (Power Rail)
< Current output up to 650 Ω load
< HART-IP and valve positioner
< Line fault detection (LFD)
< Accuracy 0.1 %



Datasheet excerpt: Technical data of  KFD2-SCD2-Ex2.LK

General specifications
Signal type Analog output
Functional safety related parameters
Safety Integrity Level (SIL) SIL 2
Systematic capability (SC) SC 3
Supply
Connection Power Rail or terminals 14+, 15-
Rated voltage 19 ... 30 V DC
Ripple ≤ 10 %
Rated current ≤ 45 mA at 24 V
Power dissipation ≤ 1 W at 20 mA and 500 Ω load
Power consumption ≤ 1 W
Input
Connection side control side
Connection terminals 7-, 8+, (9+); 10-, 11+, (12+)
Input signal 4 ... 20 mA , limited to approx. 30 mA
Input voltage open loop voltage of the control system ≤ 30 V
Voltage drop approx. 6 V at 20 mA
Input resistance field wiring open circuit : > 100 kΩ
field wiring < 50 Ω : > 100 kΩ when using terminals 1, 2 and 4, 5
Output
Connection side field side
Connection terminals 1+, 2-; 4+, 5-
terminals 3+, 2-; 6+, 5- (no short circuit detection)
Voltage ≥ 13 V at 20 mA
Current 4 ... 20 mA
Load 100 ... 650 Ω , for terminals 1, 2; 4, 5
0 ... 550 Ω , for Terminals 2, 3; 5, 6
Ripple 20 mV rms
Line fault detection breakage, load > 100 kΩ, short-circuit, load < 50 Ω
Fault indication output
Output type open collector transistor (internal fault bus)
Transfer characteristics
Deviation at 20 °C (68 °F), 4 ... 20 mA
< 0.1 % of full scale, incl. non-linearity and hysteresis
  Influence of ambient temperature < 2 µA/K (-20 ... 70 °C (-4 ... 158 °F)); < 4 µA/K (-40 ... -20 °C (-40 ... -4 °F))
Frequency range field side into the control side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB)
control side into the field side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB)
Rise time 10 to 90 % ≤ 10 ms
Galvanic isolation
Input/Output basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Input/power supply basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Input/input functional insulation, rated insulation voltage 50 V AC
Indicators/settings
Display elements LEDs
Labeling space for adhesive label at the front
Directive conformity
Electromagnetic compatibility  
  Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibility NE 21:2017
EN 61326-3-2:2018
Degree of protection IEC 60529
Protection against electrical shock UL 61010-1:2012
Ambient conditions
Ambient temperature -40 ... 70 °C (-40 ... 158 °F)
Mechanical specifications
Degree of protection IP20
Connection screw terminals
Mass approx. 135 g
Dimensions 20 x 124 x 115 mm (0.8 x 4.9 x 4.5 inch) (W x H x D) , housing type B2
  Height 124 mm
  Width 20 mm
  Depth 115 mm
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-type examination certificate BAS 00 ATEX 7240 X
  Marking Ex-Hexagon II (1)G [Ex ia Ga] IIC
Ex-Hexagon II (1)D [Ex ia Da] IIIC
Ex-Hexagon I (M1) [Ex ia Ma] I
  Output Ex ia, Ex iaD
  Voltage 25.2 V
  Current 93 mA
  Power 585.3 mW
  Internal capacitance 1.05 nF
  Internal inductance 0
Supply  
  Maximum safe voltage 250 V rms (Attention! The rated voltage can be lower.)
Input  
  Maximum safe voltage 250 V rms (Attention! The rated voltage can be lower.)
Certificate FIDI 22 ATEX 0002 X
  Marking Ex-Hexagon II 3G Ex ec IIC T4 Gc
Galvanic isolation  
  Input/Output safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
  Output/power supply safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity  
  Directive 2014/34/EU EN IEC 60079-0:2018 , EN 60079-11:2012 , EN IEC 60079-7:2015+A1:2018
International approvals
UL approval E106378
  Control drawing 116-0345 (cULus)
IECEx approval  
  IECEx certificate IECEx BAS 04.0014X
  IECEx marking [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I
Ex ec IIC T4 Gc
General information
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
 

 

更多 EC Instruments & Engineering Sdn Bhd 相关资料
EC Instruments & Engineering Sdn Bhd
EC Instruments & Engineering Sdn Bhd Electrical Instruments Johor Bahru (JB), Electronic Components Supplier Malaysia, Sensors Supply Singapore, Perak ~ EC Instruments & Engineering Sdn Bhd