SmartMeasurement’s ALCM-DT delta-tubed Coriolis mass flow meters use two tubes formed into a triangle shape, or delta, in a parallel arrangement. These delta tubes are vibrated at their resonant frequency by coils. Any mass flow passing through the tubes will generate Coriolis forces, which are created whenever a mass moves radially in a rotating system. These forces have opposite effects on the inlet and outlet sides, deforming each tube by a minor amount.
The ALCM-DT delta-tubed Coriolis mass flow meter’s circuitry also makes it possible to determine conversions such as volumetric flow, percent concentration, and percent water-cut.
Flow Range: | 150~900,000 kg/hr |
Process Connections: | Flanged (ANSI, DIN, Tri-Clamp®) |
Line Sizes: | ½”~8”(15-200 mm) |
Process temperature: | -76~662 °F (-60~350 °C) – Remote; -76~257 °F (-60~125 °C) – Integral |
Tube geometry: | Delta-Tube |
Accuracy: | ±0.5% of reading(std), 0.2% or 0.15% (opt) |
Repeatability: | ±0.05% of reading |
Engineering Units (Mass): | kg, lb, ton |
Display: | Dot-Matrix LCD |
Engineering Units (Temp.): | °C, °F |
Engineering Units: (Volume): | m³, Liter, US Gallon, Imperial Gallon |
Zero Stability: | 0.1% full-scale |
Zero Drift (%FS / °C): | 0.005 |
Max Working Pressure: | 580 psig (4.0 MPa) |
Measuring Tube Mat’l: | SS #316L |
Power Supply: | 12~28 VDC, 86~260VAC,50~60Hz |
Housing Material: | SS #304 |
Outputs: | 4-20 mA, frequency, pulse, RS485 |
Power Consumption: | Less than 12W |
Density Measuring Range: | 43.7-81.2lb/ft³ (0.7~1.3 g/cc) |
Temperature Measuring Range: | -76~662 °F (-60~350 °C) – Remote; -76~257 °F (-60~125 °C) – Integral |
Density Accuracy: | ±0.06 b/ft³ (0.001 g/cc) |
Temperature Accuracy: | ±0.5 °C |