Item |
Data |
||
APPROVAL |
/ | ||
Test standard |
IEC60947-7-1:2009/ UL1059 |
||
Pitch [mm] |
16.2 |
||
Poles |
01P |
||
IEC60947-7-1 Test data |
/ |
||
Rated voltage [V] |
1000 |
||
Rated current [A] |
125 |
||
Rated connection capacity(solid/stranded) [mm²] |
1.5-35 |
||
Surge voltage category/pollution degree/material group |
III/3/I |
||
Rated impulse voltage [KV] |
8 |
||
Rated torque [N.m] |
3.5 |
||
UL1059Test data |
/ |
||
Use group |
B |
C |
D |
Rated voltage [V] |
600 |
600 |
/ |
Rated current [A] |
150 |
150 |
/ |
Rated connection capacity (solid/stranded) [AWG] |
14-1/0 |
||
Rated torque [Lb. in] |
31 |
||
General data |
/ |
||
Screw |
M6 |
||
Inflammability class UL94 |
V-0 |
||
Ambient temperature [℃] |
-40~+105 |
||
Relative humidity |
5%-95% |
||
Inspection standard |
MIL-STD-105E II |
||
AQL |
0.65 |
||
Warranty |
12 months |
||
Material and plating |
/ |
||
Housing |
PA66 |
||
Screws |
STEEL,Zn plated |
||
Contact |
Copper alloy,Sn plated |
||
Cage |
STEEL,Zn plated |
||
Wire connecting |
|||
Recommended stripping length 17-19mm; |
|||
For solid wire, stripping wire to the appointed length, then tightening with rated torque. |
|||
For stranded wire: stripping wire to the appointed length, mating with corresponding type of ferrule, then tightening with rated torque.
|
|||
Tightening process should be steady, can’t use explosive force. |