AquaForce® High-Efficiency Indoor Liquid Screw Chiller 30HX

AquaForce® High-Efficiency Indoor Liquid Screw Chiller 30HX

分类: Carrier 当前有货
欲了解更多详情,请游览我们的官方网站 unitedfaith.com.my

详情

75 to 265 Nominal Tons

30HXA - Condenserless
30HXC - Water-Cooled

The 30HX units are high-efficiency, indoor water-cooled or condenserless chillers. The units have a quiet, low-vibration design featuring screw compressors. The 30HX chillers are compact enough to fit through a standard door, making them great replacement units.

Water-cooled chillers within the scope of the AHRI WCCL certification program are certified in accordance with the AHRI Water-Cooled Water-Chilling and Heat Pump Water-Heating Packages Certification Program, which is based on AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI). Certified units may be found in the AHRI Directory at www.ahridirectory.org. Condenserless versions of these units and 50 Hz. units below 200 Tons are not certified under the AHRI certification program.


carrier-AHRI-550-590-551-591_WCCL
carrier-iso-9001
carrier-intertek-ETL-listed-C-US

 

Performance Features

Reliability Features

Maintenance Features

Installation Features

Factory-Installed Options

  • Wye-delta start
  • Brine
  • Minus-one-pass cooler head
  • Plus-one-pass cooler head
  • Minimum load control
  • Suction service valves
  • EMM (Energy Management Module)

Field-Installed Options

  • Chilled water flow switch
  • Thermistor
  • Control power transformer
  • Remote enhanced display
  • Minimum load control
  • Chillervisor™
  • Outside temperature reset sensor
  • EMM (Energy management module)
  • BACnet translator
  • LONWorks translator

Field-Installed Accessories

  • Neoprene vibration isolators (field-installed accessory)
  • Control power transformer
  • Minimum load control
  • Sound reduction enclosure
  • Vibration isolation
  • Temperature reset sensor
  • Chillervisor™ System Manager III
  • Cooler head insulation
  • EMM (Energy Management Module)
  • Sesimic compliance option
30HXA/C Unit Size Capacity Input Power (kW) Cooler Flow Cooler Pressure Drop Condenser Flow Condenser Pressure Drop
Tons Output (kW)   gpm L/s Ft of
Water
kPa gpm L/s Ft of
Water
kPa
076 75.4 265.2 53.7 181.0 11.4 14.5 43.2 226.2 14.3 8.9 26.6
086 83.0 292.3 60.4 199.3 12.6 17.2 51.4 249.1 15.7 10.7 31.8
096 94.0 330.5 67.0 225.5 14.2 17.0 50.7 281.9 17.8 10.9 32.7
106 104.3 366.8 75.3 250.4 15.8 15.4 46.0 313.0 19.7 13.3 39.6
116 113.5 399.3 83.2 272.3 17.2 13.3 39.8 340.4 21.5 17.0 50.6
126 122.9 432.1 92.2 294.9 18.6 15.4 45.9 368.6 23.3 19.6 58.5
136 136.5 479.9 97.0 327.5 20.7 14.6 43.7 409.4 25.8 18.5 55.1
146 145.6 513.2 105.1 350.2 22.1 16.5 49.3 437.8 27.6 20.9 62.4
161 156.6 550.6 111.6 375.7 23.7 13.7 40.9 469.7 29.6 21.3 63.6
171 165.92 585.3 118.3 398.0 25.1 15.2 45.4 497.6 31.4 17.2 51.4
186 177.1 623.1 126.7 425.1 26.8 13.9 41.5 531.4 33.5 19.5 58.1
206 211.6 744.0 146.4 507.7 32.0 14.7 43.9 634.7 40.0 20.9 62.4
246 248.6 874.1 172.4 596.5 37.6 16.2 48.3 745.7 47.0 21.9 65.2
261 257.2 904.6 180.4 617.2 38.9 17.2 51.4 771.5 48.7 23.3 69.5
271 267.4 940.3 189.5 641.7 40.5 18.5 55.1 802.2 50.6 25.1 74.7
30HXA/C Unit Size Full Load Efficiency (kW/Ton) IPLV† (kw/Ton)
076 0.712 0.512
086 0.728 .0523
096 0.714 0.513
106 0.722 0.520
116 0.733 0.530
126 0.750 0.541
136 0.711 0.527
146 0.720 0.534
161 0.713 0.521
171 0.713 0.539
186 0.715 0.561
206 0.692 0.511
246 0.693 0.525
261 0.702 0.525
271 0.709 0.527

IPLV = Integrated Part Load Value
†IPLV shown is the lower of Sequence A or Sequence B unloading.

NOTES
1. Rated (60Hz unit) in accordance with AHRI Standard 550/590 at standard rating conditions.
2. Standard rating conditions are as follows:

Cooler Conditions:
Leaving Water Temperature: 44°F (6.7°C)
Flow: 2.4gpm per ton (0.043 L/s per kW)

Condenser Conditions:
Entering Water Temperature: 85°F (29.4°C)
Flow: 3.0gpm per ton (0.054 L/s per kW)

Fouling Factor (Cooler):
0.00010 hr x sq ft x °F per Btuh (0.000018m2 x K per W)

Fouling Factor (Condenser):
0.00025 hr x sq ft x °F per Btuh (0.000044m2 x K per W)

3. IPLV is a single number part load efficiency value calculated from using the efficiency values at 100%, 75%, 50%, and 25% of load when the chiller is operating in AHRI conditions.
4. All data in the above table was generated in Packaged Chiller Builder version 3.47. Please refer to the most current version of the Packaged Chiller Builder for the most up-to-date data.
5. Contact Carrier for custom ratings.