ComfortVu™ BACnet® Standard Thermostat TB-C Line Voltage Standard Models TB-C, TB-HM-C

ComfortVu™ BACnet® Standard Thermostat TB-C Line Voltage Standard Models TB-C, TB-HM-C

分类: Carrier 当前有货
欲了解更多详情,请游览我们的官方网站 unitedfaith.com.my

详情

Carrier’s ComfortVu™ BACnet thermostats offer local control of a building’s heating, ventilating and air-conditioning (HVAC) system as well as remote control from any BACnet-compliant building management system (BMS), including Carrier’s i-Vu® building automation system.

Supported Functions

Equipment Compatibility

Supported Applications (depends on available I/O)

Power Requirements 24 Vac ±15%: 4VA unit, 76 VA full load
Communication BACnet MS/TP with baud rates up to 76.8 kbps, detected and set automatically by the BACnet Thermostat. Max 127 devices.
Real-time Clock Real-time clock keeps track of time in the event of a power failure for up to 7 days
Display Backlit Touchscreen, °F or °C Selectable
Sensing Element Temperature: Range: 41° F to 95° F (5° C to 35° C) Accuracy: ±1.0° F (0.5° C)
Humidity: Range: 10% to 90% Accuracy: ±3.0% typical
Motion Sensing Sensor Type: PIR, quad, omnidirectional
Distance: 16.4 feet (5m)
Detection range: (HxV) 90° x 30°
Movement speed: 2.62 to 3.94 ft/s (0.8 to 1.2 m/s)
Detection object: 15.75 x 9.84 in. (400 x 250 mm)
Inputs T1, 0 – Normally open or normally closed dry contract, or 0-10 Vdc analog input, or 50 kOhm thermistor @ 25°C
A, B - Communication +/- (RS485)
In1, 0 - Normally open or Normally closed dry contract, or 0-10 Vdc analog input, or 50 kOhm thermistor @ 25°C
C, R - Power: 24 Vac for part numbers TB-24-C and TB-24-HM-C, or 110-220 Vac line voltage for part numbers TB-C and TB-HM-C
Outputs 11, 12, 13 – Digital outputs, 3A
14 – Digital outputs 0.3A
15, 16 - Digital Output 0.3A or Analog output 0-10 Vdc, 5 mA max., not isolated
Environmental Operating Range 50° to 122°F (10° to 50°C), 10 to 90% relative humidity, non-condensing
Compliance United States of America: FCC CFR47, Chapter 1, Subchapter A, Part 15, Class B
Canada: Industry Canada Compliant, ICES-003, Class B
Europe: Mark Low Voltage Directive: 2014/35/EU RoHS Compliant: 2011/65/EU
Australia and New Zealand: C-Tick Mark, AS/NZS 61000-6-3
CA Prop 65 Warning: This product can expose you to chemicals including Styrene and 1,3 – Propane sultone, which are known to the State of California to cause cancer. Go to www.p65warnings.ca.gov.