Wireless Motion:Lux Sensor WS-ML-902

Wireless Motion:Lux Sensor WS-ML-902

分类: Carrier 当前有货
欲了解更多详情,请游览我们的官方网站 unitedfaith.com.my

详情

As part of Carrier’s wireless sensing line, wireless motion/lux sensors are used to detect motion and light in a space. Because there are no wires to run, they can be added to your building easily.

Wireless sensors work in conjunction with a wireless adapter, which enables wireless communication between the sensors and an i-Vu® BACnet controller in the space. By sensing motion and lighting levels wirelessly, our i-Vu controllers can make smart decisions to optimize the control of heating, cooling, and lighting systems in the building, providing optimum occupant comfort and energy efficiency.

Ideal applications for the wireless motion/lux sensor include occupancy-based lighting and temperature control, as well as indoor daylight harvesting.
 

Comprehensive Capabilities

  • Wireless and battery-less space sensors (assuming sufficient lighting exists in space)
  • Maintenance-free capacitors power the sensors during unlit periods for up to 4-days without a light source
  • No repeaters or amplifiers required for zone-based applications
  • Integrates seamlessly with i-Vu® system alarming for proactive monitoring of important sensor conditions, including:
    • Sensor charge level
    • Sensor signal strength
    • Sensor offline
  • Can co-exist on Rnet with Carrier’s wired ZS sensors
  • Single-zone controllers can support a total of 5 sensors
  • Multi-zone controllers can support up to 15 sensors
Power supply Solar harvesting, internal energy storage
Supplemental battery A 1/2 AA 3.6 V 1200 mA battery is included to supplement power during commissioning and for low-light conditions
Maximum operating life Up to 4 days with no light power or battery
Time to fully charge depends on available lux
Full charge in 8 hours @ 1000 lux or 24 hours @333 lux
Protocol Customized version of EnOcean®
Radio frequency 902 MHz (North America)
Transmission range Typically, 60 ft. (18.29 m) maximum from wireless adapter, assuming sensor and wireless adapter are separated by no more than 1 drop ceiling or 2 walls (drywall with metal studs)
Transmission interval Configurable in SensorBuilder. The sensor transmits:
• On change of sensed value, and
• At a regular interval (heartbeat). The default is every 15 minutes
Minimum illumination strength 40 lux, constant
Degree of protection IP50
Operating environment -3° to 140°F (20° to 60°C) 5% to 95% relative humidity (non-condensing)
Housing ABS plastic, traffic white color
Weight 0.2 lb. (.09 kg)
Dimensions 3.17 in. W x 4.02 in. H x 1.25 in. D (8.05 cm W x 10.2 cm H x 3.18 cm D)
Compliance United States of America
FCC CFR 47, Chapter 1, Subchapter A, Part 15, Subpart B
Class B Contains FCC ID: SZV-STM300U
UL-916 (PAZX) Energy Management Equipment

Canada
Industry Canada Compliant, ICES-003, Class B
cUL Listed UL-916, PAZX7, Energy Management Equipment

Europe
EN50491-5-2:2009; Part 5-2: EMC requirements for HBES/BACS used in residential, commercial and light industry environment
EN50491-3:2009 Part 3: Electrical safety requirements for Home and Building Electronic Systems (HBES) and Building Automation and Control Systems (BACS)
Low Voltage Directive: 200695/EC RoHS Compliant: 2011/65/EU

Australia and New Zealand
C-Tick Mark AS/NZS 61000-6-3