i-Vu® MPC Open XP IO OPN-MPCXPIO48

i-Vu® MPC Open XP IO OPN-MPCXPIO48

分类: Carrier 当前有货
欲了解更多详情,请游览我们的官方网站 unitedfaith.com.my

详情

General Purpose Controller

Multipurpose programmable controller for monitoring and control of HVAC system applications. Adds additional I/O point capacity to the OPN-MPCXP controller.

The MPC Open XP IO expanders add additional I/O point capacity to the MPC Open XP controller. Flexible and versatile, the MPC Open XP controller supports multiple I/O configurations for accomplishing both common and custom HVAC control strategies. The MPC Open XP controller connects to up to 20 field points directly (8 outputs and 12 inputs), while also supporting up to 3 MPCXP IO expanders. Each MPC XP IO48 expander adds support for up to 12 additional field points (4 outputs, 8 inputs), while each MPC XP IO816 expander adds support for up to 24 additional field points (8 outputs, 16 inputs). When combined, the MPC Open XP controller and it’s associated MPC XP IO expanders can support up to 92 total points.


carrier-bacnet-international-member
carrier-bacnet-testing-laboratories

Application Features

Hardware Features

System Benefits


Specifications


 
Communication Ports Xnet Remote Expansion Port: For connecting to an MPC Open XP controller via the Xnet network.
Inputs 8 inputs
Inputs are configurable for 0-5 VDC, 0-10 VDC, 0-20 mA, thermistor (10k Type II), 1k RTD (Platinum, Nickel or Balco), and Dry Contact.
Inputs are 14 bit A/D and support up to 40 pulses per second (12.5 msec min. pulse).
Outputs

4 outputs
Outputs jumper configurable for 0-10 VDC, 0-20 mA (12 bit A/D), or 24 VDC (50 mA relay drive).
Outputs have HOA (hand/off/auto) switches, including potentiometer for manual adjustment of analog outputs.

Protection Incoming power: 2 replaceable 3 AmpPico® fuses. The power, network, and I/O are also protected against voltage transient and surge events.
Status Indicators LED status of communications, running, errors, and power.
Listed By UL-916 (PAZX), cUL-916 (PAZX7)FCC Part 15-Subpart B- Class A, CE EN50082-1997
Environmental Operating Range Operating: 0° to 140°F (-18° to 60°C), 10-90% relative humidity, non-condensing
Storage: -24°F to 140°F (-30° to 60°C), 10-90% relative humidity, non-condensing
Power Requirements 24VAC +/- 10%, 50-60Hz
45VA power consumption
26VDC (25V min, 30V max)
Single Class 2 source only, 100VA or less
Dimensions

Length: 9” (22.9 cm)
Width: 4-13/16” (12.2 cm)
Depth: 1-7/16” (3.7 cm)
Weight: 13.3 oz. (0.377 kg)

Communication Ports Xnet Remote Expansion Port: For connecting to an MPC Open XP controller via the Xnet network.
Inputs 8 inputs
Inputs are configurable for 0-5 VDC, 0-10 VDC, 0-20 mA, thermistor (10k Type II), 1k RTD (Platinum, Nickel or Balco), and Dry Contact.
Inputs are 14 bit A/D and support up to 40 pulses per second (12.5 msec min. pulse).
Outputs

4 outputs
Outputs jumper configurable for 0-10 VDC, 0-20 mA (12 bit A/D), or 24 VDC (50 mA relay drive).
Outputs have HOA (hand/off/auto) switches, including potentiometer for manual adjustment of analog outputs.

Protection Incoming power: 2 replaceable 3 AmpPico® fuses. The power, network, and I/O are also protected against voltage transient and surge events.
Status Indicators LED status of communications, running, errors, and power.
Listed By UL-916 (PAZX), cUL-916 (PAZX7)FCC Part 15-Subpart B- Class A, CE EN50082-1997
Environmental Operating Range Operating: 0° to 140°F (-18° to 60°C), 10-90% relative humidity, non-condensing
Storage: -24°F to 140°F (-30° to 60°C), 10-90% relative humidity, non-condensing
Power Requirements 24VAC +/- 10%, 50-60Hz
45VA power consumption
26VDC (25V min, 30V max)
Single Class 2 source only, 100VA or less
Dimensions

Length: 9” (22.9 cm)
Width: 4-13/16” (12.2 cm)
Depth: 1-7/16” (3.7 cm)
Weight: 13.3 oz. (0.377 kg)