i-Vu® UC Open XP OPN-UCXP

i-Vu® UC Open XP OPN-UCXP

分类: Carrier 当前有货
欲了解更多详情,请游览我们的官方网站 unitedfaith.com.my

详情

General Purpose Controller

Universal programmable controller provides auxiliary building control to interface with air handlers, chiller plants, hot water systems, lighting, and other HVAC equipment.

The UC Open XP controller provides auxiliary building control to interface with air handlers, chiller plants, hot water systems, lighting, and other HVAC equipment. The UC Open XP’s factory-engineered control programs provide simple building integration for commercial applications with 24 I/O point capability. The UC Open XP also provides support for 24 additional I/O points through the use of the UC Open XP IO Expander. When combined, these controllers can support up to 48 total I/O points for even greater flexibility.


carrier-bacnet-international-member
carrier-bacnet-testing-laboratories

Application Features

Hardware Features

System Benefits


BACNet Support Advanced application controller (B-AAC), as defined in BACNet 135-2001 Annex L
Communication Ports BACNet Port: EIA-485 port for BACnet MS/TP communications (baud rate is DIP switch selectable)
Local Access port: For system start-up and troubleshooting (115.2 kbps)
Rnet port: For connecting Carrier communicating room sensors and Carrier's touchscreen user interface
Inputs 12 inputs: Configurable for 0-10V, RTD/Thermistor/Dry contact, or 0-20mA. Inputs 1 and 2 may be used for pulse counting. All analog inputs have 12 bit A/D resolution.
Outputs 6 binary outputs: Configured as dry contact, normally open or normally closed. All binary outputs must be powered from a Class 2 power source.
6 analog outputs: 1 and 2 are configurable for 0-10V or 0-20mA; 3-6 are 0-10V only. Analog outputs have 8 bit D/A resolution.
Protection Incoming power and network connections are protected by non-replaceable internal solidstate polyswitches that reset themselves when the condition that causes a fault returns to normal. The power, network, input, and output connections are also protected against voltage transient and surge events.
Real Time Clock Battery-backed real time clock keeps track of time in event of power failure.
Battery 10-year Lithium CR2032 battery provides a minimum of 10,000 hours of trend data & time retention during power outages.
Status Indicators LED status of power, running, and errors. LED indicators for transmit/receive for BACnet port and for each of the 12 outputs.
Controller Addressing Rotary DIP switches set BACnet MS/TP MAC address of controller.
Listed By UL-916, FCC Part 15-Subpart B- Class A, CE EN50082-1997
Environmental Operating Range Operating: -24° to 140°F (-30° to 60°C), 10-90% relative humidity, non-condensing
Storage: -24°F to 140°F (-30° to 60°C), 10-90% relative humidity, non-condensing
Power Requirements 24VAC +/- 10%, 50-60Hz
20VA power consumption
26VDC (25V min, 30V max
Single Class 2 source only, 100VA or less
Dimensions Length: 11-13/16” (30 cm)
Width: 5” (12.7 cm)
Depth: 2” (5.1 cm)
Weight: 1.1 lbs. (0.50 kg)