with Puron® Refrigerant (R-410a)
5 to 20 Nominal Tons
The 09XC indoor remote air-cooled condenser units are designed for vertical installation with rear return air and horizontal air discharge. These units provide a practical and economical approach to comfort conditioning requirements in replacement, renovation, and new construction applications.
Performance Features
-
Capacities of 7½, 10, and 15tons will match with 5 to 15 ton 50XCR remote units
-
ASHRAE 90.1 compliant
-
Adjustable belt-drive centrifugal condenser fan for high-static capability
-
Fan controlled by 24-volt control system
-
Designed for R-410A refrigerant
-
Fully insulated unit
Reliability Features
-
Aluminum fin/copper tube coils
-
Painted weather-resistant cabinet meets 500-hour salt spray requirements
-
Adjustable belt-drive fan motors
-
Unit is ETL and ETL, Canada certified
-
Manufactured in an ISO 9000 certified factory
Installation Features
-
Shipped with nitrogen charge
-
Flanges provided on condenser inlet and outlet
-
Single point electrical connection
Maintenance Features
-
Ducted or free return connections
-
All service can be done through unit front or side panels
-
Permanently lubricated TEFC (totally enclosed fan cooled) condenser fan motors
Field-Installed Accessories
AHRI Capacity Ratings
Size |
Nominal Capacity (Tons) |
Condenser Airflow (Cfm) |
Heat Rejection (Btuh) |
Total Power (kW) |
08 |
7.5 |
4500 |
126800 |
1.10 |
12 |
10 |
6000 |
169200 |
1.86 |
16 |
15 |
7500 |
253600 |
2.19 |
AHRI = Air Conditioning, Heating and Refrigeration Institute
Weights & Dimensions
Size |
Operating Weight (lb) |
Dimensions (in) |
Width |
Height |
Depth |
08 |
527 |
53.1 |
46.6 |
30.0 |
12 |
732 |
68.0 |
54.5 |
31.2 |
16 |
956 |
88.0 |
54.5 |
31.2 |