Network analyzer UPA41 is a performance metering & monitoring device that provides all of the measurements needed to complete energy efficiency projects and to assure the monitoring of electrical distribution. It is particularly suitable for consumption analysis and control, with an excellent quality/price ratio.
With its large backlit multiple-display screen with 6 hot keys, the instrument is easy to use. Furthermore, it is provided with a correction function for CT wiring errors.
The instrument can be equipped with additional modules for RS485 communication, additional digital or analogue inputs/outputs and temperature detection can be used to increase its range of functionality.
The instrument is compliant with IEC 61557-12, the reference standard for PMDs (Performance Metering & monitoring Devices).
TECHNICAL SPECIFICATIONS
Auxiliary power supply
Auxiliary power supply
Alternative voltage 110 …400 VAC
AC tolerance ± 10 %
Direct current 120 … 350 VDC / 12 … 48 VDC
DC tolerance ± 20 % / – 6 … + 20 %
Frequency 50 / 60 Hz
Power consumption ≤ 10 VA
Voltage measurements (trms)
Direct measurement between phases 50 to 500 VAC
Direct measurement between phase and neutral 28 to 289 VAC
Measurement of currents on insulated inputs (trms)
Via CT primary 9,999 A
Via CT secondary 1 or 5 A
Energy accuracy
Active (according to IEC 62053-22) Class 0.5 S
Reactive (according to IEC 62053-23) Class 2
Frequency measurement
Measurement range 45 … 65 Hz
Size & weight
W x H x D: 96 x 96 x 60 mm, max 400 g