General specifications
|
Signal type
|
Digital Input
|
Functional safety related parameters
|
Safety Integrity Level (SIL)
|
SIL 2
|
Supply
|
Connection
|
terminals 23, 24
|
Rated voltage
|
20 ... 90 V DC / 48 ... 253 V AC 50 ... 60 Hz
|
Power dissipation/power consumption
|
≤ 2 W ; 2.5 VA / 2.2 W ; 3 VA
|
Interface
|
Programming interface
|
programming socket
|
Input
|
Connection side
|
field side
|
Connection
|
Input I: intrinsically safe: terminals 1+, 3-
Input II: non-intrinsically safe: terminals 13+, 14-
|
Input I
|
sensor acc. to EN 60947-5-6 (NAMUR) or mechanical contact
|
|
Pulse duration
|
> 50 µs
|
|
Input frequency
|
0.001 ... 5000 Hz
|
|
Line fault detection
|
breakage I ≤ 0.15 mA; short-circuit I > 6.5 mA
|
Input II
|
startup override: 1 ... 1000 s, adjustable in steps of 1 s
|
|
Active/Passive
|
I > 4 mA (for min. 100 ms) / I < 1.5 mA
|
|
Open circuit voltage/short-circuit current
|
18 V / 5 mA
|
Output
|
Connection side
|
control side
|
Connection
|
output I: terminals 10, 11, 12
output II: terminals 16, 17, 18
outout III: terminasl 19+, 20-
output IV: terminals 8+, 7-
|
Output I, II
|
signal, relay
|
|
Contact loading
|
250 V AC / 2 A / cos φ ≥ 0.7 ; 40 V DC / 2 A
|
|
Mechanical life
|
5 x 107 switching cycles
|
|
Energized/De-energized delay
|
approx. 20 ms / approx. 20 ms
|
Output III
|
electronic output, passive
|
|
Contact loading
|
40 V DC
|
|
Signal level
|
1-signal: (L+) - 2.5 V (50 mA, short-circuit/overload proof)
0-signal: switched off (off-state current ≤ 10 µA)
|
Output IV
|
analog
|
|
Current range
|
0 ... 20 mA or 4 ... 20 mA
|
|
Open loop voltage
|
max. 24 V DC
|
|
Load
|
max. 650 Ω
|
|
Fault signal
|
downscale I ≤ 3.6 mA , upscale ≥ 21.5 mA (acc. NAMUR NE43)
|
Transfer characteristics
|
Input I
|
|
|
Measuring range
|
0.001 ... 5000 Hz
|
|
Resolution
|
0.1 % of the measurement value , ≥ 0.001 Hz
|
|
Accuracy
|
0.1 % of the measurement value , > 0.001 Hz
|
|
Measuring time
|
< 100 ms
|
|
Influence of ambient temperature
|
0.003 %/K (30 ppm)
|
Output I, II
|
|
|
Response delay
|
≤ 200 ms
|
Output IV
|
|
|
Resolution
|
< 10 µA
|
|
Accuracy
|
< 20 µA
|
|
Influence of ambient temperature
|
0.005 %/K (50 ppm)
|
Galvanic isolation
|
Input I/other circuits
|
reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
|
Output I, II/other circuits
|
reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
|
Mutual output I, II, III
|
reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
|
Output III/power supply
|
reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
|
Output III/start-up override
|
basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff
|
Output III/IV
|
basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff
|
Output IV/power supply
|
reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
|
Start-up override/power supply
|
reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
|
Interface/power supply
|
reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
|
Interface/output III
|
basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff
|
Indicators/settings
|
Display elements
|
LEDs , display
|
Control elements
|
Control panel
|
Configuration
|
via operating buttons
via PACTware
|
Labeling
|
space for labeling at the front
|
Directive conformity
|
Electromagnetic compatibility
|
|
|
Directive 2014/30/EU
|
EN 61326-1:2013 (industrial locations)
|
Low voltage
|
|
|
Directive 2014/35/EU
|
EN 61010-1:2010
|
Conformity
|
Electromagnetic compatibility
|
NE 21:2006
|
Degree of protection
|
IEC 60529:2001
|
Input
|
EN 60947-5-6:2000
|
Ambient conditions
|
Ambient temperature
|
-20 ... 60 °C (-4 ... 140 °F)
|
Mechanical specifications
|
Degree of protection
|
IP20
|
Connection
|
screw terminals
|
Mass
|
300 g
|
Dimensions
|
40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) (W x H x D) , housing type C2
|
|
Height
|
119 mm
|
|
Width
|
40 mm
|
|
Depth
|
115 mm
|
Mounting
|
on 35 mm DIN mounting rail acc. to EN 60715:2001
|
Data for application in connection with hazardous areas
|
EU-type examination certificate
|
TÜV 99 ATEX 1471
|
|
Marking
|
II (1)G [Ex ia Ga] IIC
II (1)D [Ex ia Da] IIIC
I (M1) [Ex ia Ma] I
|
Supply
|
|
|
Maximum safe voltage
|
253 V AC / 125 V DC (Attention! Um is no rated voltage.)
|
Input I
|
terminals 1+, 3-: Ex ia
|
|
Voltage Uo
|
10.1 V
|
|
Current Io
|
13.5 mA
|
|
Power Po
|
34 mW (linear characteristic)
|
Input II
|
terminals 13+, 14- non-intrinsically safe
|
|
Maximum safe voltage Um
|
40 V (Attention! The rated voltage can be lower.)
|
Output I, II
|
terminals 10, 11, 12; 16, 17, 18 non-intrinsically safe
|
|
Maximum safe voltage
|
253 V (Attention! The rated voltage can be lower.)
|
|
Contact loading
|
253 V AC/2 A/cos φ > 0.7; 40 V DC/2 A resistive load (TÜV 99 ATEX 1471)
|
Output III
|
terminals 19+, 20- non-intrinsically safe
|
|
Maximum safe voltage Um
|
40 V (Attention! Um is no rated voltage.)
|
Output IV
|
terminals 8+, 7- non-intrinsically safe
|
|
Maximum safe voltage
|
40 V DC (Attention! Um is no rated voltage.)
|
Interface
|
RS 232
|
|
Maximum safe voltage
|
40 V (Attention! Um is no rated voltage.)
|
Galvanic isolation
|
|
|
Input I/other circuits
|
safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
|
Directive conformity
|
|
|
Directive 2014/34/EU
|
EN IEC 60079-0:2018 , EN 60079-11:2012
|
International approvals
|
FM approval
|
|
|
Control drawing
|
16-538FM-12
|
IECEx approval
|
|
|
IECEx certificate
|
IECEx TUN 04.0007
|
|
IECEx marking
|
[Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I
|
General information
|
Supplementary information
|
Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
|