Input
|
Rated voltage and frequency
|
3 phases: 380v; 50/60Hz
|
|
Allowable range
|
Voltage fluctuation range: ±15%; voltage unbalance: <3%; frequency: 47~63 Hz
|
Output
|
Output voltage
|
3-phase, 0V~input voltage, with the error less than 5%.
|
|
Output frequency range
|
V/F control: 0.00~650.00Hz
Vector control: 0.00~200.00Hz
|
Basic specifications
|
Motor control mode
|
V/F control without PG, V/F control with PG, vector control without PG, vector control with PG, V/F separate control
|
Steady-state speed precision
|
Vector control without PG: ≤1%
Vector control with PG: ≤0.02%
|
Starting torque
|
Not less than 150% of rated torque at 0.50Hz
|
Overload capacity
|
150% of rated current for 1 minute
|
Frequency resolution
|
Digital reference: 0.01Hz Analog reference: 0.1% of max. frequency
|
Output frequency precision
|
Analog reference: : ±0.2% of max. frequency(25±10℃)
Digital reference: 0.01Hz(-10~+40℃)
|
Command source
|
Keypad, terminal and communication. They can be switched over by terminals
|
Frequency reference source
|
Keypad, communication, UP/DOWN value, AI1, AI2, PFI and arithmetic unit
|
Auxiliary frequency reference
|
Achieves flexible frequency setting
|
Torque boost
|
Auto or manual torque boost
|
V/F curve
|
User defined V/F, linear V/F and 5 reduced-torque curves
|
Accel/decel
|
Linear or S-curve acceleration/deceleration
|
Jog
|
Jog frequency: 0.10~50.00Hz
Jog accel/decel time: 0.1~60.0s
|
Auto energy saving
|
V/F curve is optimized automatically based on the load condition, achieving auto energy-saving run
|
AVR
|
Keeps the output voltage constant automatically when the voltage of power grid fluctuates
|
Auto carrier regulation
|
Carrier frequency is regulated automatically based on the load characteristic and ambient temperature
|
Random PWM
|
Regulates the tone of the motor noise
|
Droop control
|
Applicable to cases where multiple inverters drive the same load
|
Momentary power failure
|
Ensures uninterrupted operation by controlling the DC link voltage
|
|
DC braking
|
Braking time: 0.0~60.0s
Braking current: 0.0~100.0% of rated current
|
|
PFI
|
Highest input frequency: 50kHz
|
|
PFO
|
Open-collector pulse(square wave) output of 0~50kHz, programmable
|
|
Analog input
|
2 channels of analog input, voltage or current type, positive or negative
|
|
Analog output
|
2 channels of analog output, 0/4~20mA or 0/2~10V, programmable
|
|
Digital input
|
8 channels of optional multi-function digital input(leakage/source type)
|
|
Digital output
|
2 channels of optional multi-function digital output(leakage/source type); 2 channels of multi-function relay output
|
|
Communication
|
Built-in RS485 port, supporting Modbus protocol and USS commands
|
Characteristic functions
|
Process PID
|
Two sets of PID parameters; multiple correction modes; free PID function
|
Multiple PLC modes
|
User can set 8 PLC run modes, with each having up to 48 stages. The mode can be selected by terminals. PLC status can be saved at power failure.
|
Multi-speed select mode
|
4 selection modes. Refer to F4-17
|
User defined menu
|
30 user parameters can be defined
|
Parameter display change
|
Can display parameters different from the default ones
|
Torque control
|
Torque/speed control can be switched by terminals. Multiple torque setting modes.
|
|
Zero-servo
|
Zero-speed position can be locked
|
Characteristic functions
|
High-speed UP/DOWN counter
|
Synchronous control, counting in production, stop contol by count and precise position control can be realized
|
High-speed meter counter
|
Stop control by length and length indication can be achieved
|
Wobble
|
Ensures even winding of textiles
|
Programmable unit
|
Comparator, logic unit, trigger, arithmetic unit, filter, multiple-way switch, timer
|
kWh meter timer
|
For adjustment of optimal energy saving strategy
|
Protection functions
|
Overcurrent, overvoltage, undervoltage, input/output phase loss, output short-circuit, overheating, motor overload, external fault, analog input disconnection, stall prevention, etc.
|
Options
|
Braking unit, remote control box, digital I/O expansion board, encoder interface board, analog input expansion board, keypad with copying function or potentiometer, keypad mounting box, keypad extension line, I/O reactor, EMI filter, Profibus-DP module, etc.
|
Ambient
|
Service site
|
Altitude less than 1000 meters; indoor; no direct sunlight; free of dust, corrosive gases, inflammable gases, oil mist, water vapor, water drops, salt mist, etc.
|
Temperature/humid
|
-10~+40℃/20~90%RH, no condensation
|
Storage temperature
|
-20~+60℃
|
|
Vibration
|
Less than 5.9m/s2 (0.6g)
|
Structure
|
Protection degree
|
IP30
|
Cooling method
|
Forced air cooling, with fan control
|