LG Hausys Floors
|
TECHNICAL DATA |
Static Pulse |
|
Item |
Standard Test Method |
Specification |
Conductive Tile |
Dissipative Tile |
Electrical/ Electrostatic Properties |
Electrical Resistance |
ESD S 7.1 |
Static Conductive : 2.5 x 104 ~ 106Ω |
2.5 x 104 ~ 106Ω |
106 ~ 109Ω |
|
ASTM F 150 |
Static Dissipative :
106 ~ 109Ω |
|
|
|
|
|
Static Generation |
AATCC-134 |
|
0.1KV |
0.2KV |
|
|
|
|
|
Static Decay |
Federal Test Method
101B Method 4046 |
< 0.5 sec |
0.01 sec |
0.01 sec |
Other Properties |
Classifcation |
EN 685 |
|
Class 34 + 43 |
|
|
|
|
Composition Of Material |
ASTM F 1700,
Certifcate of Compliance |
|
Homogeneous |
|
|
|
|
Thickness |
ASTM F 386, EN 428 |
as specifed ± 0.13mm |
Meets Standard |
|
|
|
|
Nominal Sizes |
ASTM F 536, EN 427 |
<± 0.4mm / 304.8mm |
Meets Standard |
|
|
|
|
Squareness |
ASTM F 2055 |
maximum 0.25mm |
Meets Standard |
|
|
|
|
Residual Indentation |
ASTM F1914, EN 433 |
average less than 8%,
max. single reading 10% |
< 8 % |
|
|
|
|
Flexibility |
ASTM F 137 |
no crack or break |
No crack or break |
|
|
|
|
Dimensional Stability |
ASTM F 2199, EN 434 |
< 0.51mm / 304.8mm |
Meets Standard |
|
|
|
|
Resistance To Chemicals |
ASTM F 925, EN 423 |
No more than a slight change in surface dulling, surface attack, or staining |
no more than a slight change in surface
dulling, surface attack, or staining |
|
|
|
|
Resistance To Heat |
ASTM F 1514 |
ΔE < 8 ave., max |
Meets Standard |
|
|
|
|
Resistance To Light |
ASTM F 1515 |
ΔE < 8 ave., max |
Meets Standard |
|
|
|
|
Static Load Limit |
ASTM F 970-93 |
- |
0.005”(at 2500 psi), 0.127mm(at 175kgf/cm2) |
|
|
|
|
Smoke Density |
ASTM E 662 |
< 450 |
< 450 |
|
|
|
|
Flame Spread |
ASTM E 84, NFPA 225 |
|
< 75 |
|
|
|
|
Thermal Conductivity |
DIN 52612 |
|
0.309 W/(m.k) |
|
|
|
|
Critical Radiant Flux |
ASTM E 648, NFPA 253 |
|
Class 1 ( > 0.45 w/cm2) |
|
|
|
|
Abrasion Resistance |
ASTM D 1044, CS-10-F Wheel, 500gm Weights |
|
Cycl |
% Gauge Loss |
|
|
|
2,500 |
0.22 |
|
|
|
5,000 |
0.44 |
|
|
|
7,500 |
0.65 |
|
|
|
10,000 |
0.86 |
|
|
|
|
Resistance To Wear |
EN 660-1 |
|
Group M |
|
|
|
|
Castor Chair Suitablilty |
EN 425 |
|
No damage |
|
|
|
|
Color Fastness |
EN ISO 105 B02 |
|
At least 6 |
|
|
|
|
Standard For Health Care Facilities |
NFPA 99 |
|
Confrms to the requirement of NFPA 99 in effect at the time of installation |
|
|
|
|
Fulflls Product Requirements |
EN 649 |
|
Yes |
|
|
|
|
Underwriters Laboratories |
UL 779 |
|
Meets UL Standard |
|
|
|
|
Burning Characteristics |
EN 13501-1 |
|
Bfl-S1 |
|
|
|
|
Warranty |
|
|
|
|
|
|
|
Guarantee For Manufacturing
Defects And Wear-Out* |
No Damage |
|
5 Years |
|
|
|
|
Conductivity* |
|
|
Lifetime |
|
|