CD-30M/30I |
CD-30M/30I are designed for air conditioning system being installed on air conditioning duct system. With built-in transmitter, CD-30M/30I can detect CO2 gas density using NDIR (Non Dispersive Infrared) and convert the measured density signal into linear current or voltage signal to be transmitted to external monitoring unit or controlling unit such as PLC or DDC.
|
|
|
|
[ Features ] |
Non Dispersive Infrared(NDIR) CO2 sensor |
highest detection accuracy and the longest sensor life time with the least affection from other gases. |
Built-in transmitter |
Built-in transmitter transforms the sensor signal into stable standard current output signal (4-20mA) to be transmitted to external controlling equipments such as PLC or DDC. |
Robust metal housing |
RS-485 enables stables stable and long distance (maximum 1.2km) signal communication. |
|
[ Sensor options ] |
|
|
Measurement range |
accuracy(±) |
0~2,000ppm / 0~5,000ppm |
30ppm ± 5% rel. |
0~2.00% |
200ppm ± 5% rel. |
|
|
|
[ Specification ] |
|
|
|
CD-30M |
CD-30I |
Mounting type |
Wall mounting |
Duct mounting |
Detection principle |
NDIR (Non-Dispersive Infrared) |
Detection method |
Diffusion |
Response time |
within 20 seconds, 90%/full scale |
Accuracy |
≤2% /full scale |
Zero variance |
<±0.3% / full scale / year |
Measurement range |
0~2,000ppm / 0~5,000ppm / 2.00% |
Output |
4-20mA |
D/A resolution |
12bit |
D/A accuracy |
Voltage mode: ±2% / reading ±20mV, current loop: ±2% / reading ±0.3mA |
Input power |
24V AC/DC ±20%, 50~60Hz |
Power consumption |
≤3W |
Signal wire |
CVVS & CVVSB 1.25sq X 3 wire – shield type |
Terminal |
Screw terminal |
Housing |
Metal case with metal tube |
Operation temperature / humidity |
0~50℃ / 0~95% RH (non-condensing) |
Initialization time |
Within 1 min |
|