Fluke 1621 Earth Ground Tester

Fluke 1621 Earth Ground Tester

Kategori: Earth Ground Tester Tersedia
Untuk maklumat lanjut, lawati laman web rasmi kami di mobicon.my

Penerangan

Earth Ground Tester for resistance measurement

The Fluke 1621 is an easy-to-use earth ground tester. For ground resistance testing, the 1621 is the first line of defense in detecting reliable ground connections. The unit features basic ground testing methods including 3-pole Fall-of-Potential as well as 2-pole ground resistance tests. Its convenient size, rugged holster, and large, clear LCD display make it an ideal field earth ground tester, for most electrical grounding work environments. With a simple user interface and intuitive functionality, the Fluke 1621 is a handy grounding tool for electrical contractors, utility test engineers, and earth ground specialists.
 

General specifications
Measuring functions
   3-pole earth ground resistance, 2-pole ac resistance of a conductor, Interference voltage
Intrinsic error
   Refers to the reference temperature range and is guaranteed for one year
Measuring rate
   2 measurements/second
Battery[1]
   One 9 volt alkaline (LR61)
Battery condition
   LO-BAT is displayed if voltage drops below 6.5 V
Voltages
Between jacks H/C2 and E/C1:  250 Veff maximum (effective voltage)
Between jacks S/P2 and E/C1:  250 Veff maximum
Climatic class
   VDE/VDI 3540 RZ (conforming to KWG as per DIN 40040, 4/87)
Temperature performance[2]
Working:  -10 °C to +50 °C (+14 °F to +122 °F)
Operating:  0 °C to +35 °C (+32 °F to +95 °F)
Storage:  -20 °C to +60 °C (+68 °F to +140 °F)
Reference:  +23 °C ± 2 °C (+73 °F ± 4 °F)
Temperature coefficient
   ± 0.1 % of range per degree Kelvin
Safety
   IEC/EN 61010-1, 600 V CAT II, pollution degree 2
Dimensions
   113 mm x 54 mm x 216 mm (4.5 in x 2.1 in x 8.5 in), including holster
Weight
   850 g (1.9 lb), including standard accessories, volume approximately 600 cm3
Note:
   [1]If the tester is not going to be used, or is being stored for a long period, remove the battery and store separately from the tester to avoid damage from battery leakage.
Note:
   [2]The four temperature ranges for the tester exists to satisfy European Standards requirements; the instrument can be used over the full working temperature range by using the temperature coefficient to calculate accuracy at the ambient temperature of use.

 

Electrical specifications
Maximum deviations:
E1 Influence factor  Position
E1 Deviation influence  0 %
E2 Influence factor  Supply voltage
E2 Deviation influence  0 %
E3 Influence factor  Temperature E3
E3 Deviation influence  2.3 %
E4 Influence factor  Serial interference voltage (20 V)
E4 Deviation influence  0.6 %
E5 Influence factor  Probe- and auxiliary probe resistance
E5 Deviation influence  10 %
Test voltage
   3.7 kV
Protection type
   IP 40; IEC/EN 60529
Electromagnetic compatibility
   Emission: IEC/EN 61326 Class B
   Immunity: IEC/EN 61326 Annex C
RE resistance measurement
Measuring method  Current-voltage measurement with improved cross-talk attenuation, no compensation of measuring lead resistance, with probe (3-pole) or without probe (2-pole), as per IEC/EN 61557-5
Open circuit voltage  23 to 24 V ac
Short circuit current  > 50 mA ac
Measuring frequency  128 Hz
Maximum permissible overload  250 Veff
Measuring time
   8 seconds (average from when START is pressed)
Limit input
   Tester retains set value even if instrument is turned off (assuming battery power supply is sufficient)
Automatic changeover of resolution
RH  < 7 kΩ
Resolution  0.01 Ω
RH  < 50 kΩ
Resolution  0.1 Ω
RH  > 50 kΩ
Resolution  1 Ω
Interference voltage display dc + ac
Vmax  30 Veff
Common mode rejection  > 80 dB at 50 Hz and 60 Hz
Ri  680 kΩ
Measuring uncertainty  < 10 % for pure ac and dc signals

 

 

Measuring range
0.15 Ω to 20 Ω
Resolution  0.01 Ω
Display range  0 to 19.99 Ω
200 Ω
Resolution  0.1 Ω
Display range  20 to 199.9 Ω
2 kΩ
Resolution  1 Ω
Display range  200 to 1999 Ω
Intrinsic uncertainty
   ± (6 % of measured value + 5D)
Operating uncertainty IEC 61557[1]
   ± (18 % of measured value + 5D)
Notes:
   [1] Covers all deviations caused by influence quantities E1-E5.
If the deviation E4 caused by high probe or auxiliary probe resistance is higher than specified flashes.
Measured values are outside of the specified operating uncertainty.



Lebih maklumat tentang Mobicon - Remote Electronic Sdn Bhd
Mobicon - Remote Electronic Sdn Bhd
Mobicon - Remote Electronic Sdn Bhd Measuring Instruments Selangor, Soldering Iron & Switches Supply Kuala Lumpur (KL), Audio Equipment Supplier Malaysia ~ Mobicon - Remote Electronic Sdn Bhd