Length | 1670 mm (three phase) |
Height | 44 mm (1U) |
Depth | 51 mm |
Weight | 3 kg |
Nominal Input Voltage | 230 / 400 V rms |
Max. Input Current | 16 A rms per phase |
Input Frequency | 50 - 60 Hz |
Input Cable/Plug | 2.5m (other lengths on request) CEE 16A 5p 6h |
Nominal Input Voltage | 230 / 400 V rms |
Max. Output Current | 16 A rms per phase |
Output Connections | 36 x C13 & 6 x C19 |
Integrated Filter/Switch | No (optional on request) |
Powerline | Reliable narrowband Powerline Communication (Cenelec B, FCC or ARIB) |
Ethernet | 10/100 Mbps Fast Ethernet, RJ-45 connector (HTTP, SNMP, Telnet, NTP) |
Serial | Console on left RJ12 connector, 115’200 bps, 8n1 |
Technology | TFT full graphical color display, 320x240 |
Refresh Rate | 1 Hz |
Screen Saver | Display turned-off automatically after 15 minutes |
Internal | Temperature |
External | 2 extension ports for temperature and humidity sensors |
Accuracy | [%] | 1% (IEC 1036 Class 1) | |
P | [W] | Real power per phase & total | |
Q | [VAR] | Reactive power per phase & total | |
S | [VA] | Apparent power per phase & total | |
Ep | [kWh] | Real energy per phase & total | |
Eq(C) | [kVARh] | Reactive energy (Capacitive) per phase & total | |
Eq(L) | [kVARh] | Reactive energy (Inductive) per phase & total | |
Urms | [V] | Line voltage per phase | |
Irms | [A] | Alarm | Output current per phase, Neutral, total |
Upk | [V] | Alarm | Peak line voltage per phase |
f | [Hz] | Alarm | Line frequency per phase |
PF | N/A | Power factor per phase | |
Ti, T1, T2 | [°C] | Alarm | Internal temperature and values from external temperature sensors |
H1, H2 | [%] |
Humidity values from external sensors |