The Single Duct Air Terminal Zone Controller provides dedicated control functions for single duct terminals with modulating heat or up to 2 stages of heat. The zone controller is part of the Carrier ComfortID system.
Field wiring is 18 to 22 AWG (American Wire Gage). The zone controller is a NEC (National Electronic Code) Class 2 rated device.
The power supply is 24 VAC ± 10% at 40 VA (50/60 Hz).
The power requirement sizing allows for accessory water valves and for the fan contactor. Water valves are limited to 15 VA on both single-position and modulating hot water. The fan contactor is limited to 10 VA (holding) each.
Terminal airflow (nominal cfm) is rated at 1-in. wg (249 kPa) measured velocity pressure. The zone controller is capable of controlling to as low as 10% or as high as 125% of nominal airflow with an accuracy of ± 3% (nominal) at any point within the range.
FLASH EPROM
0 to 2.0 in. wg (0 to 498 kPa) maximum for the onboard flow sensor.
The zone controller space temperature range is –40 to 245 F (–40 to 118 C). The zone controller has an allowable control set point range from 40 to 90 F (4 to 32 C) for heating and 45 to 99 F (7 to 37 C) for cooling.
The number of controllers is limited to 128 zones maximum, with a limit of 8 systems (Linkage Coordinator configured for at least 2 zones). Bus length may not exceed 4000 ft (1219 m), with no more than 60 devices on any 1000 ft (305 m) section. Optically isolated RS-485 repeaters are required every 1000 ft (305 m).
At 19,200 and 38,400 baud, the number of controllers is limited to 128 maximum, with no limit on the number of Linkage Coordinators. Bus length may not exceed 1000 ft (305 m).
Operating Temperature: 32 to 140 F (0° to 60 C) at 0 to 90% RH (non–condensing) Shipping Temperature: –40 to 185 F (-40 to 85 C) at 0 to 90% RH (non–condensing)
Performance vibration:
Office environment. Indoor use only.