Thermocouple |
Inputs |
Type K |
-58 to 2498°F (-50 to 1370°C) |
Type J |
-58 to 1832°F (-50 to 1000°C) |
Type B |
32 to 3272°F ( 0 to 1800°C) |
Type T |
-454 to 752°F (-270 to 400°C) |
Type E |
-58 to 1382°F (-50 to 750°C) |
Type R or S |
32 to 3182°F ( 0 to 1750°C) |
Type N |
-58 to 2372°F (-50 to 1300°C) |
Type C |
-58 to 3272°F (-50 to 1800°C) |
PT100Ω RTD (DIN) |
-328 to 1652°F (-200 to 850°C) |
PT100Ω RTD (JIS) |
-328 to 1202°F (-200 to 650°C) |
Control/Alarm Relay |
5 Amp @ 110V, SPST (resistive load) |
DC Current Output |
4-20mA (resistive); Impedance < 600 ohms |
Accuracy |
Thermocouple: ±1.8°F (1ºC); RTD: ±0.36°F (0.2ºC) |
Sampling Time |
Four (4) samples per second |
LED Display |
Two 4-digit displays for Process Value, Setpoint, and programming modes |
LED Status |
Alarm and Control output status |
Control Modes |
Fuzzy Logic enhanced three-term PID with Auto Tune |
• Proportional Band 0 to 300.0% |
• Integral time 0 to 3600 seconds |
• Derivative time 0 to 900 seconds |
• Hysteresis 0.0 to 200.0 or 0.0 to 2000 |
• Cycle time 1 to 100 seconds |
Front Panel |
Lexan construction, Drip/Dust proof; IR rating: IEC IP63 |
Power Supply |
90 to 264 VAC; 50/60 Hz (< 5VA power consumption) |