Earth resistance
measurement |
20Ω |
200Ω |
2000Ω |
|
Measuring range |
0.00 - 2000 Ω |
Display range |
0.00 - 20.99 Ω |
0.0 - 209.9 Ω |
0 - 2099 Ω |
Accuracy*1 |
±1.5%rdg±0.08 Ω*2 |
±1.5%rdg±4dgt |
Auxiliary earth resistance*3 |
<10kΩ |
<50kΩ |
<100kΩ |
Comparator reference value |
10Ω |
100Ω |
500Ω |
Earth voltage measurement |
|
Measuring range |
0 - 300 V AC (45 - 65Hz) |
±0 - ±300 V DC |
Display range |
0.0 - 314.9 V |
0.0 - ±314.9 V |
Accuracy |
±1%rdg±4dgt |
Overload protection |
Earth resistance : 360V AC (10 seconds) |
Earth voltage : 360V AC (10 seconds) |
Applicable Standards |
IEC 61010-1, CAT IV 100 V /CAT III 150 V /CAT II 300 V Pollution degree 3 |
IEC 61010-2-030,IEC 61010-031, IEC 61557-1, -5 |
IEC 60529 IP67, IEC 61326-1, -2-2, EN50581(RoHS) |
Power source |
LR6(AA)(1.5V) × 6 |
Dimensions |
121(L) × 188(W) × 59(H) mm (including case lid) |
Weight |
Approx. 690g (including batteries and case lid) |
Accessories
for 4105DL |
7127B(Simplified measurement probe) |
8041(Auxiliary earth spikes[2 spikes/1set]) |
9121(Shoulder strap) |
7267(Cable reel for Earth resistance tester (red)) |
7268(Cable reel for Earth resistance tester (yellow)) |
7271(Earth resistance test leads) |
9190(Carrying case) |
LR6(AA) × 6, Instruction manual |
Accessories
for 4105DL-H |
7127B(Simplified measurement probe) |
8041(Auxiliary earth spikes[2 spikes/1set]) |
9121(Shoulder strap) |
7266(Earth resistance test leads[red-20m, yellow-10m, green-5m/1set]) |
9191(Hard case) |
LR6(AA) × 6, Instruction manual |
Optional |
7272(Precision measurement Cord set) |
8259(Adapter for measurement terminal) |