Function |
Range |
Resolution |
Measuring range |
Accuracy |
Earth resistance
Re
(Rg at
ρ measurement) |
2Ω |
0.001Ω |
0.03 - 2.099Ω |
±2%rdg±0.03Ω |
20Ω |
0.01Ω |
0.03 - 20.99Ω |
±2%rdg±5dgt (*1) |
200Ω |
0.1Ω |
0.3 - 209.9Ω |
2000Ω |
1Ω |
3 - 2099Ω |
20kΩ |
10Ω |
0.03k - 20.99kΩ |
200kΩ |
100Ω |
0.3k - 209.9kΩ |
Auxiliary earth resistance
Rh, Rs |
|
|
|
8% of Re+Rh+Rs |
Earth resistivity
ρ |
2Ω |
0.1Ω·mm - 1Ω·m
Autoranging |
0.2 - 395.6Ω·m |
ρ=2×π×a×Rg (*2) |
20Ω |
0.2 - 3956Ω·m |
200Ω |
20 - 39.56kΩ·m |
2000Ω |
0.2 - 395.6kΩ·m |
20kΩ |
2.0 - 1999kΩ·m |
200kΩ |
Series interference voltage
Ust (A.C only) (*3) |
50V |
0.1V |
0 - 50.9Vrms |
±2%rdg±2dgt (50/60Hz) |
±3%rdg±2dgt (40 - 500Hz) |
Frequency
Fst |
Autoranging |
0.1Hz
1Hz |
40Hz - 500Hz |
±1%rdg±2dgt |
Measuring method |
Earth resistance: Fall-of-potential method
(currents and voltages measured via the Probes)
Measurement method of Earth Resistivity (ρ): Wenner 4-pole method
Series interference voltage (earth voltage)
RMS Rectifier (between the E-S Terminals) |
Memory capacity |
800 data |
Communication Interface |
Model 8212-USB Optical Adaptor |
LCD |
Dot-matrix 192×64 monochrome |
Over-range Indication |
''OL'' |
Overload Protection |
between E-S(P) and between E-H(C) terminals AC280V / 10 sec. |
Applicable standards |
IEC 61010-1 CAT III 300V, CAT IV 150V Pollution degree 2
IEC 61010-031, IEC 61557-1, 5, IEC 61326-1 (EMC), IEC 60529 (IP54) |
Power source |
DC12V : sizeAA manganese dry battery (R6) × 8
(Auto power off: approx. 5 minutes) |
Dimensions |
167(L) × 185(W) × 89(D) mm |
Weight |
approx. 900g (including batteries) |
Accessories |
7229A (Earth precision measurement),
7238A (Simplified measurement test leads),
8032 (Auxiliary earth spikes [2 spiks/set])×2 sets (4 spikes in total),
8200-04 (Cord reel [4 pcs])×1 set,
8212-USB (USB adaptor with ''KEW Report(Software)''),
9121 (Shoulder strap),
9125 (Carrying case),
R6 × 8, Instruction manual, Calibration certificate |