Features : Industrial grade class sensor comes with high accuracy and long-term stability.
Input : Capacitive Humidity Sensor & Pt100
Output : Temp. RTD ( Pt100 / NTC10K ) /
Humidity 0 ... 10 V ; 4 ... 20 mA
Accuracy : Temp. ±0.3°C+ 0.002°C x t actual /
Humidity ( at +25°C ) ±3 %RH (30 ... 70 %RH ) of F.S. /
Humidity ( at +15 ... 35°C ) ±5 %RH ( 20 ... 80 %RH ) of F.S.
Measuring Range : 0 ... 50 °C;5 ... 95 %RH
●Additional option (ILAC/TAF) Test report - Standard Calibration laboratory(Leb number: 3032)
Description
● Compact design and easy to install
● An economical choice, high C/P ratio
● Industrial class sensor comes with high accuracy and long-term stability
Specification
Measuring Range : 0 ... 50 °C;5 ... 95 %RH
Recommended measuring range : 15 ... 35 °C ; 20 ... 80 %RH
Accuracy : ± 0.3℃+0.002℃ x t actual ;
± 3 %RH ( 30 ... 70 %RH ) of F.S. , at +25℃ ;
± 5 %RH ( 20 ... 80 %RH ) of F.S. , at+ 15 ... 35℃
Output : Temp. : RTD ( Pt100 / NTC10K ) ; Humidity : 0 ... 10V;4 ... 20mA
Signal connection : 3-wire : Temp. / Humidity : ( 0 ... 10 V ) ;
2-wire : Humidity : ( 4 ... 20mA ) ; 4-wire : Temp.
Load Resistance : 0 ... 10V;≧10KΩ / 4 ... 20mA:RL<(+V-10)/0.02 < 500Ω
Output calibration ( ZERO ) adjustment degree : 10% of zero-point and full-range
Power supply : 3-wire : 24VDC ± 20% ; 2-wire : 9 ... 28VDC
IP rating : IP24
Features
· Compact design and easy to install
· An economical choice, high C/P ratio
· Industrial grade class sensor comes with high accuracy and long-term stability
Application
· Monitoring for HVAC process / Air conditioning / Environmental ventilation control
· Environmental monitoring for building / Factory / Clean / room / Laboratory
· Monitoring for storeroom / Crisper / Agriculture / Food industry
· Temperature and humidity measuring in machinery or equipment