FLUKE - T6-600 ELECTRICAL TESTER

FLUKE - T6-600 ELECTRICAL TESTER

Kategori: Tersedia
Untuk maklumat lanjut, lawati laman web rasmi kami di carlssoon-tech.com

Penerangan

FLUKE - T6-600 ELECTRICAL TESTER
Brand : Fluke
Model : T6-600


Product Description


Working in cramped electrical boxes and trying to find a safe metallic contact points is often challenging. The Fluke T6-600 Electrical Tester with FieldSense™ technology, lets you quickly and safely take measurements by sliding the open fork over a conductor, without the need for test leads. The T6-600 works with wires up to AWG 4/0 (120 mm2) with a 17.8 mm jaw opening.

Technical Specification


Measurement Specifications
 
Function Requires test leads Range Resolution Accuracy[1]
FieldSense
ac voltage true-rms
No 600 V 1 V ±(3% + 3 counts) 45 Hz - 66 Hz[2] [3]
FieldSense
ac current true-rms
No 200.0 A 0.1 A ±(3% + 3 counts) 45 Hz - 66 Hz
FieldSense
frequency (Hz)
No   1 Hz ±(1% + 2 counts)[3]
Volts ac true-rms Yes 600 V 1 V ±(1.5% + 2 counts) 45 Hz - 66 Hz
Volts dc Yes 600 V 1 V ±(1% + 2 counts)
Resistance Yes 2000 Ω 1 Ω ±(1% + 2 counts)
Safety   600 V CAT III

Accuracy[1]: ± ( [ % of reading] + [number of least significant digits] ). Accuracy is specified for 1 year after calibration, at 18 °C to 28 °C (64 °F to 82 °F) with relative humidity to 90 %. AC measurements are ac-coupled, RMS responding.

Accuracy[2]: Add 3 % without an external ground connection. External ground connection required for user wearing insulated gloves, standing on an insulated ladder, or otherwise insulated from earth ground.

Accuracy[3]: FieldSense is specified from 16 V to 100 % of range.


General Specifications
 
Calibration 1-year calibration cycle
Dimensions 61.1 x 259.3 x 43.8 mm
Jaw opening 17.8 mm
Weight 0.35 kg (0.78 lb)
Temperature Operating -10 °C to +50 °C (14 °F to 122 °F)
Storage -30 °C to +60 °C (-22 °F to +140 °F)
Altitude Operating 2,000 m (6,562 feet)
Storage 10,000 m (32,808 feet)
Relative Humidity 0% to 90%, 5 °C to 30 °C (41 °F to 86 °F)
0% to 75%, 30°C to 40 °C (86 °F to 104 °F)
0% to 45%, 40°C to 50 °C (104 °F to 122 °F)
Battery Type and Life 2 x AA (IEC LR6); 360 hours continuous, typical; 200 hours using FieldSense
Temperature coefficient 0.1 x (specified accuracy) / °C for <18°C or >28 °C
(< 64.4 °F or > 82.4 °F)
Safety IEC/EN 61010-1: Pollution Degree 2
Electromagnetic Environment IEC/EN 61326-1: Portable

Lebih maklumat tentang Carlssoon Technologies (Malaysia) Sdn Bhd
Carlssoon Technologies (Malaysia) Sdn Bhd
Carlssoon Technologies (Malaysia) Sdn Bhd Testing Equipment Supplier Melaka, Measuring Instrument Supply Malaysia, Lab Supplies Ayer Keroh ~ Carlssoon Technologies (Malaysia) Sdn Bhd