Product type description | SRB211ST (V2) |
Article number (order number) | 101208309 |
EAN (European Article Number) | 4030661448923 |
eCl@ss number, version 12.0 | 27-37-18-19 |
eCl@ss number, version 11.0 | 27-37-18-19 |
eCl@ss number, version 9.0 | 27-37-18-19 |
ETIM number, version 7.0 | EC001449 |
ETIM number, version 6.0 | EC001449 |
Available until | 31.12.2024 |
|
IFA cULus CCC TILVA |
Standards |
EN IEC 62061 EN ISO 13849-1 EN IEC 60947-5-1 EN IEC 60947-5-3 EN IEC 60947-5-5 EN IEC 61508 EN IEC 60204-1 EN IEC 60947-1 |
Climatic stress | EN 60068-2-78 |
Housing material | Glass-fibre reinforced thermoplastic, ventilated |
Gross weight | 280 g |
Electronic Fuse | Yes |
Wire breakage detection | Yes |
Cross-circuit detection | Yes |
Removable Terminals | Yes |
Start input | Yes |
Feedback circuit | Yes |
Automatic reset function | Yes |
Reset edge detection | Yes |
Earth connection detection | Yes |
Integral system diagnostics, status | Yes |
Number of LEDs | 6 |
Number of normally closed (NC) | 2 |
Number of safety contacts | 3 |
Number of Safety contacts, STOP 0 | 3 |
Number of Safety contacts, STOP 1 | 2 |
Number of signalling outputs | 1 |
Safety classification |
Standards |
EN IEC 60947-5-1 EN IEC 61508 |
Stop-Category |
0 1 |
Safety classification - Relay outputs |
Performance Level, stop 0, up to | e |
Performance Level, stop 1, up to | d |
Category, Stop 0 | 4 |
Category, Stop 1 | 3 |
Diagnostic Coverage (DC) Level, Stop 0 | ≥ 99 % |
Diagnostic Coverage (DC) Level, Stop 1 | > 60 |
PFH value, Stop 0 | 2.00 x 10⁻⁸ /h |
PFH value, Stop 1 | 2.00 x 10⁻⁷ /h |
Safety Integrity Level (SIL), Stop 0, suitable for applications in | 3 |
Safety Integrity Level (SIL), Stop 1, suitable for applications in | 2 |
Mission time | 20 Year(s) |
Common Cause Failure (CCF), minimum | 65 |
PFD value | 5.30 x 10⁻⁵ |
PFD value | 5.30 x 10⁻⁵ |
Mechanical life, minimum | 10,000,000 Operations |
Mounting | Snaps onto standard DIN rail to EN 60715 |
Terminal designations | IEC/EN 60947-1 |
Termination |
rigid or flexible Screw terminals M20 x 1.5 |
Cable section, minimum | 0.25 mm² |
Cable section, maximum | 2.5 mm² |
Tightening torque of Clips | 0.6 Nm |
Width | 22.5 mm |
Height | 100 mm |
Depth | 121 mm |
Degree of protection of the enclosure | IP40 |
Degree of protection of the mounting space | IP54 |
Degree of protection of clips or terminals | IP20 |
Ambient temperature | -25 ... +60 °C |
Storage and transport temperature | -40 ... +85 °C |
Resistance to vibrations | 10...55 Hz, Amplitude 0.35 mm, ± 15 % |
Restistance to shock | 30 g / 11 ms |
Rated impulse withstand voltage Uimp | 4 kV |
Overvoltage category | III |
Degree of pollution | 2 |
Frequency range |
50 Hz 60 Hz |
Operating voltage |
24 VAC -15 % / +10 % 24 VDC -15 % / +20 % |
Ripple voltage | 10 % |
Rated operating voltage | 24 VAC |
Rated operating voltage | 24 VDC |
Rated AC voltage for controls, 50 Hz, minimum | 20.4 VAC |
Rated control voltage at AC 50 Hz, maximum | 26.4 VAC |
Rated AC voltage for controls, 60 Hz, minimum | 20.4 VAC |
Rated control voltage at AC 60 Hz, maximum | 26.4 VAC |
Rated AC voltage for controls at DC minimum | 20.4 VDC |
Rated control voltage at DC, maximum | 28.8 VDC |
Electrical power consumption | 2.4 W |
Electrical power consumption | 5.9 VA |
Contact resistance, maximum | 0.1 Ω |
Note (Contact resistance) | in new state |
Drop-out delay in case of power failure, typically | 80 ms |
Drop-out delay in case of emergency, typically | 30 ms |
Pull-in delay at automatic start, maximum, typically | 250 ms |
Pull-in delay at RESET, typically | 20 ms |
Material of the contacts, electrical | AgSn0, Ag-Ni, self-cleaning, positive drive |
Voltage, Utilisation category AC-15 | 230 VAC |
Current, Utilisation category AC-15 | 6 A |
Voltage, Utilisation category DC-13 | 24 VDC |
Current, Utilisation category DC-13 | 6 A |
Switching capacity, minimum | 10 VDC |
Switching capacity, minimum | 10 mA |
Switching capacity, maximum | 250 VAC |
Switching capacity, maximum | 8 A |
Voltage, Utilisation category AC-15 | 230 VAC |
Current, Utilisation category AC-15 | 3 A |
Voltage, Utilisation category DC-13 | 24 VDC |
Current, Utilisation category DC-13 | 2 A |
Switching capacity, minimum | 10 VDC |
Switching capacity, minimum | 10 mA |
Switching capacity, maximum | 250 VAC |
Switching capacity, maximum | 6 A |
Conduction resistance, maximum | 40 Ω |
Voltage, Utilisation category DC-12 | 24 VDC |
Current, Utilisation category DC-12 | 0.1 A |
Switching capacity, maximum | 24 VDC |
Switching capacity, maximum | 2 A |
EMC rating | EMC-Directive |
Indicated operating states |
Position relay K2 Position relay K1 Internal operating voltage Ui Position relay K3/K4 |
Note (applications) |
Safety sensor Guard system Emergency-Stop button Pull-wire emergency stop switches Safety light curtain |
Note (General) | Inductive loads (e.g. contactors, relays, etc.) are to be suppressed by means of a suitable circuit. |
Note (Wiring diagram) |
The wiring diagram is shown with guard doors closed and in de-energised condition. Automatic start: The automatic start is programmed by connecting the feedback circuit to the terminals X1/X3. If the feedback circuit is not required, establish a bridge. Input level: The example shows a 2-channel control of a guard door monitoring with two position switches, whereof one with positive break, external reset button (R) and feedback circuit (H2). The control recognises cross-short, cable break and earth leakages in the monitoring circuit. For 1-channel control, connect NC contact to S11/S12 and bridge S12/S22 Connect potential p-type outputs of safety light grids/curtains to S12/S22. The devices must have the same reference potential. The safety enabling circuit 37/38 conforms to EN 60204-1 for STOP Category 1. The safety enabling circuits 13/14 and 23/24 conform to EN 60204-1 for STOP Category 0. F1 = Hybrid fuse |