The FS-7000RF Remote Microphone Interface Panel is used to connect the FS-7000RM Remote Microphone to the FS-7000 Series Voice Evacuation System. Up to 4 FS-7000RMs can be connected.

Specification:

Power Source 24 V DC, M3 screw terminal, distance between barriers: 6.4 mm
Current Consumption 60 mA
No. of Speaker Control Lines Max. 50 lines
Priority Control Last-in-1st-out priority/1st-in-1st-out priority/individual priority/
no priority (selectable)
Group Broadcast Broadcast possible to up to 20 groups by connecting optional FS-7000GM.
No. of Connectable FS-7000RM Units Max. 4, M3.5 screw terminal, distance between barriers: 7.2 mm
Cable Distance Total 800 m max.
Display Section Power indicator, Fault indicator
Operating Temperature 0℃ to +40℃
Operating Humidity Under 90% RH (no condensation)
Finish Panel: Aluminum, black, alumite
Dimensions 482 (W) × 88.4 (H) × 334.7 (D) mm
Weight 4.2 kg
Accessory Connection cable (6 pins, 2.5 m) …1, Connection cable (10 pins, 2.5 m) …1,
Removable terminal plug (3 pins) …1