The 50BVW indoor water-cooled packaged units are designed for vertical installation, a variety of airflow configurations, and cooling only operation. The modularity of these units provides a versatile and economical approach to comfort conditioning requirements in replacement, renovation, and new construction applications.
Indoor Self-Contained Units
30 to 60 Nominal Tons
Size | Nominal Cooling Capacity (Tons) | Gross Cooling Capacity (Btuh) | Nominal Airflow (Cfm) | EER | Nominal Water Flow (gpm) | Heat Pump Heating (Btuh) | Fan (HP) | Weight (lbs) | Dimensions (in) | ||
---|---|---|---|---|---|---|---|---|---|---|---|
Length | Width | Height | |||||||||
034 | 30 | 385000 | 9000 | 14.4 | 90 | 425000 | 15 | 2580 | 69-3/4 | 51-5/8 | 117-1/4 |
044 | 40 | 500600 | 12000 | 14.1 | 120 | 680000 | 2@10 | 4334 | 139-1/2 | 51-5/8 | 117-1/4 |
054 | 50 | 651600 | 15000 | 14.6 | 150 | 800000 | 2@15 | 5198 | 139-1/2 | 51-5/8 | 117-1/4 |
064 | 60 | 769900 | 18000 | 13.8 | 180 | 850000 | 2@15 | 5230 | 139-1/2 | 51-5/8 | 117-1/4 |