The GEMINI® 38AU series outdoor units and matched with the 40RU series indoor air handlers offer a wide variety of options for your HVAC application needs. This series is designed for long dependable operation whether it's a rooftop or on-the-ground installation. All GEMINI 38AU Condensing Units and 40RU Fan Coils use environmentally sound Puron® refrigerant. Together, they create a reliable split system that provides easy solutions to a wide range of commercial HVAC needs.
with Puron® Refrigerant
10 to 20 Nominal Tons
Unit | Cooling Stages | Nominal Capacity (Tons) | Net Cooling Capacity (MBH) | Total Power (kW) | EER | IEER |
---|---|---|---|---|---|---|
38AUD12/40RUA12 | 2 | 10 | 117.0 | 10.4 | 10.3 | 11.6 |
38AUD14/40RUA14 | 2 | 12.5 | 148.0 | 13.4 | 11.0 | 12.0 |
38AUD16/40RUA16 | 2 | 15 | 184.0 | 16.4 | 11.2 | 11.8 |
38AUD25/40RUA25 | 2 | 20 | 240.0 | 21.6 | 11.0 | 11.2 |
AHRI = Air-Conditioning, Heating and Refrigeration Institute
ASHRAE = American Society of Heating, Refrigerating and Air Conditioning, Inc.
EER = Energy Efficiency Ratio
IEER = Integrated Energy Efficiency Ratio
COP = Coefficient of Performance
NOTES
1. Rated in accordance with ARI Standard 340/360---07, as appropriate.
2. Ratings are based on:
- Cooling Standard: 27°C (80°F) db, 19°C (67°F) wb indoor air temp and 35°C (95°F) db outdoor air temp.
- IEER Standard: 27°C (80°F) db, 19°C (67°F) wb indoor air temp and 4 various outdoor temperatures.
3. All units comply with ASHRAE 90.1 Energy Standard for minimum EER and IEER requirements.