DC260-12 Deep-Cycle AGM Battery

DC260-12 Deep-Cycle AGM Battery

Category: DC Series Available
For more information, visit our official website at superb-access.com.my

Description

Cycling Capacity
20 hour rate: 260 Amp Hours
Reserve Capacity
@ 25 Amps: 578 minutes
@ 75 Amps: 145 minutes
Mechanical Specifications
Group Size: 8D
Terminal Type: L (Flag) or APW (Dual Marine)
Total Height: 8.82″ (224 mm)
Height: 8.66″ (220 mm)
Width: 10.59″ (269 mm)
Length: 20.51″ (521 mm)
Weight: 170.6 lbs (77.4 kg)
Case Type: ABS Plastic – Flame Res Rating UL94-HB
Electrical Specifications
Nominal Voltage: 12 Volt
Capacity @ 100 hour rate: 286 AH
Capacity @ 20 hour rate: 260 AH
Capacity @ 10 hour rate: 234 AH
Capacity @ 5 hour rate: 214 AH
CCA: 1525 Amps
CA or MCA: 1830 Amps
PHCA: 2600 Amps
Short Circuit Current: 5810 Amps
Internal Resistance: 1.8m Ω

Discharge Table (Constant Current)

Time Amps Rate
20 hr 13 0.05 CA
10 hr 23.4 0.1 CA
8 hr 28.3 0.13 CA
5 hr 42.3 0.25 CA
3 hr 58.9 0.33 CA
2 hr 78.3 0.5 CA
1 hr 148 1 CA

Charge Voltages

Charge Stage Battery Voltages-12V Battery Voltages-24V Battery Voltages-36V Battery Voltages-48V
Bulk 14.7 V 29.4 V 44.1 V 58.8 V
Absortion 14.7 V 29.4 V 44.1 V 58.8 V
Float 13.6 V 27.2 V 40.8 V 54.6 V
TC Factor: -4mV/°C/cell

Temperature Range Specifications

Condition Recommended Maximum
Storage -15°C to 50°C -40°C to 71°C
Operation -15°C to 40°C -40°C to 71°C
Charge with TC -15°C to 50°C -40°C to 71°C
Charge without TC 0°C to 40°C -15°C to 50°C

Terminal Torque Specifications

Terminal Type ft-lbs in-lbs Nm
AP | DT (AP) | M6 | M6M (stud) | TP07 (AP) | TP08 (AP) 4.2 – 6.0 50 – 70 5.6 – 7.9
FR45 6.0 – 7.5 70 – 90 7.9 – 10.1
M8 7.1 – 8.0 85 – 95 9.6 – 10.7
DT (stud) | M10M (stud) 9.2 – 10.4 110 – 125 12.2 – 14.0

More detail about Superb Access Solutions Sdn Bhd
Superb Access Solutions Sdn Bhd
Superb Access Solutions Sdn Bhd Scaffolding Supplier Selangor, Aerial Work Platform Supply Kuala Lumpur (KL), Aluminium Tower System Rental Malaysia ~ Superb Access Solutions Sdn Bhd
Contact Us flagMalaysia