DISPLAY ・Color LCD 3.5 inches dot matrix.
ATT ・Anti-Trip Technology (with 2 & 3 wire) for no trip LOOP L-PE testing on all RCDs.
・With 2 wire only, very useful in case of no Neutral (i.e. 3-phase motor lines).
LOOP ・High test current range of 2Ω with 0.001Ω resolution.
・Zs Limit compares the values required by Electrical Installations Standard with
measured results.
RCD ・Type AC, A, F, B(General & Selective), EV and Variable RCDs.
・Single and Auto test, Ramp test and Contact voltage.
EARTH ・Earth resistance test 2 and 3 wires with all accessories included.
INSULATION ・Resistance test 100, 250, 500 & 1000V with auto discharge voltage.
CONTINUITY ・Continuity test at 200mA or 15mA with selectable buzzer for fast judgment.
PHASE ROTATION ・On 3-phase lines with clear indication of the sequence on the display.
VOLTS ・TRMS Voltage measurements 2-600V, Mains Frequency.
HELP ・Display shows how to connect the instrument according to the function selected.
SPD ・Surge Protection Device test, for SPD that uses varistor.
PAT ・Portable Appliance Tester function, for Insulation and Protective conductor resistance test
SAFETY ・IEC 61010-1 CAT IV 300 V, CAT III 600 V. IEC 61557-1,2,3,4,5,6,7,10.
※1 7187A:British plug, 7218A:(EU)European SHUKO plug, 7221A:(SA)South african plug, 7222A:(AU)Australian plug
Various features
Large LCD & HELP function
-
All the test data is shown in one large colored screen.
-
HELP function will show how to connect the instrument according to the function selected
Operation in 3 simple steps & Hands free testing
-
Set the rotary dial to your testing range.
-
Connect the instrument to the installation under test.
-
Press the test button.(By remote probe or using the Lockdown function of the test button.)
Anti-Trip Technology (with 2 & 3 wire)
For no trip LOOP L-PE testing on all RCDs.
With 3 wire (L, N, PE), to get the best accuracy readings.
With 2 wire only, very useful in case of no Neutral (i.e. 3-phase motor lines).
Loop Impedance 0.001 resolution
High test current range of 2Ω with 0.001Ω resolution.
Zs/Ra Limit
Zs Limit compares the values required by Electrical Installations Standard with measured results.
The verification of safety requirement on an electrical installation is simplified by using Zs/Ra Limit function. This function will automatically check if the measured loop impedance for TN (or earth loop for TT) is low enough to trip (disconnect) the MCB / Fuse / RCD giving the result of PASS or FAIL on the display.
SPD test
SPD (Surge Protection Device) which contains varistor can be tested measuring the tripping voltage without damage it.
PAT test
PAT test (PAT = Portable Appliance Tester) It is possible to check the insulation resistance and earth bond continuity of portable appliances for class I and II.
Connectivity
Use the PC application KEW Report to inprove work efficiency.
KEW 6516 can download the test data by connecting the USB adaptor (Model 8212-USB) and then print complete Test Reports by a PC.