eYc THS88MAX Industrial High Pressure Dew Point Transmitter

eYc THS88MAX Industrial High Pressure Dew Point Transmitter

Category: Dew Point Transmitter Available
For more information, visit our official website at improtechonline.com

Description

Max. scaling range : Dew point-100 ... +60 dp°C
Linear accuracy : ±1 dp°C (at -20 ... +20 dp°C)
±1.5 dp°C(at -40 ... +20 dp°C)
±2 dp°C (at -60 dp°C)
Reference (at -100 ... -60 dp°C)
Power supply : DC 24 V±15%
Installation : 1/2’’PT, 1/2’’G, and 5/8’’UNF
IP rating : IP65(ProbeIP20)
●YUDEN-TECH CO.,LTD. Calibration Laboratory - ( ILAC / TAF ) Test report, for more detailed information please contact us.
(TAF accreditation3032, complying with ISO / IEC 17025 ) TAF has mutual recognition arrangement with ILAC MRA
 
Description

-Features

Dew point calibration, highly accuracy, 4 ... 20 mA and RS-485 output
Reduce insensitivity temperature zone, quickly response
Hysteresis compensation, resistance to moisture, extreme high and low humidity impact
EMC anti-interference, anti-condensation, low-temperature influence, long-term stability
Three thread (1/2’’PT, 1/2’’G, and 5/8’’UNF) mode can be selected
 
Specification

Input
Input type : Capacitive humidity sensor & Pt100
Operating range of dew point : -100 ... +60 dp°C

Output
Max. scaling range : Dew point-100 ... +60 dp°C
Dew point switch to another physical quantity range : 
                                                                                    Frost point-60 ... 0 fp°C
                                                                                    Absolute humid.(Volume)0 ... 50000 ppm/v
                                                                                    Absolute humid.(Weight)0 ... 50000 ppm/w
Output signal : Standard RS-485 & 1 analog output 4 ... 20 mA / 0 ... 10 V
Signal connection : 3-wire
Linear accuracy : ±1 dp°C (at -20 ... +20 dp°C)
                             ±1.5 dp°C(at -40 ... +20 dp°C)
                             ±2 dp°C (at -60 dp°C)
                             Reference (at -100 ... -60 dp°C)
Load resistance : Current outputMax.500 ΩVoltage output:Min.10 KΩ

Electrical
Power supply : DC 24 V±15%
Current consumption : DC 24 V, 50 mA
Electrical connection : M12 connector

Environment
Output calibration (ZERO & SPAN) adjustment range : Software 
Response time t90(Temp. at+25°C) : 20 sec
Medium : Air
Operating Temp. for housing : -40 ... +60°C
Operating Humid. for housing : 0 ... 95%RH (Non-condensing)
Operating Temp. for probe : -40 ... +60°C
Storage temperature : -25 ... +60°C
Pressure resistance : 16 bar

Installation
Installation : 1/2’’PT, 1/2’’G, and 5/8’’UNF

Protection
IP rating : IP65(ProbeIP20)
Electrical protection : ■ Polarity protection ■ Over-voltage ■ Short-circuit

Material
Housing : S.S.(SUS304)
Probe : S.S.(SUS304)SUS sintered filter(SUS316)
Weight : 168 g
 
Application
Compressed air system / Air separation equipment / Freezer / Adsorption machine / Plastic dryer / Industrial drying process / Paper / Chemical process monitoring
 

More detail about TECH IMPRO AUTOMATION SOLUTION SDN BHD
TECH IMPRO AUTOMATION SOLUTION SDN BHD
TECH IMPRO AUTOMATION SOLUTION SDN BHD Industrial Automation Supplier Malaysia, Flow Meter Supply Penang, Pressure Transmitter Supplies Butterworth ~ TECH IMPRO AUTOMATION SOLUTION SDN BHD
Contact Us flagMalaysia