Description
Three-phase 500VAC 60A
General-purpose Book type
High-attenuation from 150kHz to 1MHz
1-stage filter
Features of FTA-60
Space-saving type
Maximum input voltage 528VAC: 10% fluctuations in voltage 480VAC
Selectable leakage current value
Ordering Information and Options
FTA(1) - 60(2) - 683(3) - □(4)
(1) Model Name
(2) Rated Current
(3) Line to ground capacitor code
Refer to Product Line-up.
* When the line to ground capacitor code is different, the attenuation characteristic is
different.
(4) Option
H:Ultra high attenuation type
335 is not applied.
U:lmprove differential mode attenuation (Rated voltage 250V)
G:With switch of line to ground capacitor
Only 335 is applied.
* Leakage current
Switch state is ON (switched to “|”) 160mA/250mA max
Switch state is OFF (switched to “○”) 10μA/16μA max
Product Line-up
Product Name |
Leakage Current* |
Line to ground capacitor
(nominal value) |
FTA-60-223 |
1.0mA/2.0mA max |
22,000pF |
FTA-60-683 |
2.5mA/5.0mA max |
68,000pF |
FTA-60-104 |
3.5mA/7.0mA max |
100,000pF |
FTA-60-335 |
160mA/250mA max |
3.3μF |