COSEL FSB-20

COSEL FSB-20

Category: 3ph Input Available
For more information, visit our official website at improtechonline.com

Description

Three-phase 500VAC 20A
Book type
EMI/EMC Filter for motor drive system
2-stage filter

Features of FSB-20

Improve saturation resistance
Space-saving type
Maximum input voltage 528VAC: 10% fluctuations in voltage 480VAC
Selectable leakage current value
Push down type terminal block

Ordering Information and Options

FSB(1)  -  20(2)  -  324(3)  -  (4)  

(1) Model Name
(2) Rated Current
(3) Line to ground capacitor code
  Refer to Product Line-up.
  * When the line to ground capacitor code is different, the attenuation characteristic is
    different.
(4) Option
  H:Ultra high-attenuation type
  U:Improve differential mode attenuation (Rated voltage 250V) Only 573, 254,
    335 is applied.

Product Line-up

Product Name Leakage Current* Line to ground capacitor
(nominal value)
FSB-20-203 1.0mA/2.0mA max
0.1mA/0.2mA max
CY1: 0.01μF, CY2: 0.01μF
FSB-20-693 2.5 mA/5.0mA max
0.35mA/0.7mA max
CY1: 0.022μF, CY2: 0.047μF
FSB-20-104 3.5mA/7.0mA max
0.5mA/1.0mA max
CY1: 0.033μF, CY2: 0.068μF
FSB-20-324 12 mA/24 mA max
1.5mA/3.0mA max
CY1: 0.1μF, CY2: 0.22μF
FSB-20-355 180mA/270mA max
25 mA/50 mA max
CY1: 0.22μF, CY2: 3.3μF

Specification

Contents Specifications
Rated Voltage Three-phase Three-wire 500V 50/60Hz
Rated Current 20A
Operating Temperature -40 to +85℃ (Refer to Derating Curve)
Agency Approvals UL1283, CSA C22.2 No.8 (C-UL) , DIN EN60939 VDE0565 Teil3-1, ENEC
Others Dimensions (WxHxD) 66x100x240 mm [2.60x3.94x9.45 inches]
Weight 1.8kg max
Warranty Period 5-year