APPLICATIONS:
DESCRIPTION & FEATURES:
Output Signal |
4/20 mA, 2-wire / V = 10.5-55 Vdc 4/20 mA + HART, 2-wire / V = 16.5-55 Vdc 1/5 Vdc, 3-wire / V = 10.5-55 Vdc Modbus, 4-wire / V = 9-30 Vdc |
LCD Display | Available with LCD display (standard) or without LCD display (optional) |
Accuracy | 0.075% URL standard, 0.05% optional |
Stability | 0.2% per 5 years |
Temperature Range |
Working: -40/85°C (with display -20/70°C), -40/185°F (with display -4/158°F) Storage: -40/110°C (with display -40/85°C), -40/230°F (with display -40/185°F) Media: silicone oil filling: -40/120°C (-40/248°F) |
Working Humidity | 5-100% at 40°C (104°F) |
Pressure Connection | 1/4” or 1/2” NPTM or F, 1/4” or 1/2” GM (large 12mm orifice) |
Housing | Rugged die-cast aluminum housing, painted blue |
Wetted Parts | 316L SS with PTFE o-ring (Hastelloy® C optional) |
Overload Pressure | Maximum of 3,600 or 6,000 psi |
Power Consumption | </- 500 mW @ 24 VDC, 20.8 mA |
Vibration |
20g, 20Hz…5kHz According to GB/T 1827.3 / IEC 61298-3 tests, <0.1% URL |
Shock | 20g, 20Hz…5kHz |
Available Pressure Units | kPa, Mpa, bar, psi, mmHg, mmH2O, mH2O, inH2O, ftH2O, inHg, mHg, TORR, mbar, g/cm2, kg/cm2, Pa, ATM |
Available Temperature Units | Celsius, Fahrenheit |
Protection Class | EMI, ESD, RFI, reverse polarity protected |
Approvals |
CSA, for USA & Canada • Class I, Division 1, Group A,B,C and D T6 | Class II, Division 1 Group E, F and G T80oC | Class III Intertek, for USA & Canada • Class I, Zone 0 A Ex ia IIC T6 Gb | Class I, Division 1, Group A-D, T6 | – 40oC to 60oC |
Protection Class | IP66 / IP67 |
Weight | 8.8 lbs (4.0 kg) |
Operational Life | 100 million cycles |