TOR-5 - Click to view details

TOR-5 - Click to view details

Category: TOR-5 Available
For more information, visit our official website at gridvisiontnd.com

Description

Description

Diagnostic mode

GlobeCore technology for diagnostic evaluation of transformers status is based on measuring some parameters by means of sensors, calculating other important parameters in reliance on these data, and transmitting all the results to the end user.
Interpretation of the results of online measurements of transformer parameters is available in the web application. We can always see what range measured and calculated values are within. But critical damage can develop in a matter of days and hours, and if the deterioration of parameters is observed on a day off work, or the transformer is very far away, you may never get a change to purify and dry the oil. Specifically for such cases, TOR-5 unit is equipped with a system for drying and filtering the insulating oil. When the transformer parameters reach the values set by the operator, TOR-5 automatically switches from the diagnostic evaluation mode to the insulating oil filtration and drying mode.

GlobeCore monitoring technique is based on using the relative humidity of insulating oil. Water can enter the transformer from the environment, for example, due to seal leaks; therefore, TOR-5 system measures the following parameters by means of sensors once a minute, 24 hours a day, 7 days a week:


A high-precision hydrogen sensor is additionally used as an indicator of transformer malfunctions. Hydrogen is formed in oil as one of the first gases already at the temperature of 150 degrees Celsius and accounts for up to 59% of all the gases released during the decomposition of oil molecules. Therefore, the content of this gas in insulating oil is a rather informative parameter for diagnostic evaluation of possible transformer malfunctions, in particular, occurring partial discharges. With partial discharges in oil, the weakest hydrocarbon bonds are broken through ionization with accumulation of hydrogen.

All measured data are transmitted via the Internet to a cloud server using a high-speed router. The router contains specialized software run in Linux environment. This software receives several analyzed parameters from sensors via Modbus/RS485 protocol and transfers them via HTTPS protocol. The router is connected to the Internet via any 2G/3G/LTE mobile network available at the location of the equipment.

On the cloud server, other parameters are calculated using special formulas and give more complete information about the transformer status: Thus, the quantity of information parameters available in TOR-5 system is greater than the quantity of installed sensors due to the application of calculation algorithms. More parameters allow going beyond the scope of simple assessment of water content in the transformer and proceeding to assess various risks associated with the presence of water in oil and paper insulation.

Oil Drying and Filtration mode
In this mode, the oil is taken from the transformer bottom; next, it is sequentially pumped through a filter with the filtration fineness of ten microns and three adsorbers (sorbent cartridges) each of which contains 15 kilograms of aluminosilicate sorbent consisting of granules with a microporous structure. Using a filter, mechanical impurities are removed from the oil, and the aluminosilicate sorbent absorbs and retains water molecules in its crystals. After that, pure and dry oil is fed to the top of the transformer tank. The process of absorbing and entrapping the water does not require heating the oil and runs with the same efficacy regardless of the temperature. The pumping speed is 30 liters per hour, and the oil is processed without disconnecting the transformer, regardless of the time of day, weather conditions, or the presence of maintenance staff.
After the oil parameters return to normal, TOR-5 unit automatically switches back from the oil filtration and drying mode to the parameters monitoring mode.
Due to the fact that the water in the transformer is in a state of constant migration from oil to paper insulation and vice versa, the circulation of oil through the adsorbers allows removing the water not only from the oil, but also from the paper insulation. Thus, owing to TOR-5 system, the transformer remains dry throughout its service life.

Standard Complete
A standard complete set of TOR-5 system includes: TOR-5 system is connected to the transformer using hoses or pipelines. The connection is made by one person via camlock quick couplings in a few minutes. Connection to radiator fins is also possible. TOR-5 can be connected to any oil-filled transformer regardless of brand and operational life.

Specification
Item Value
Performance, L/h 30
Amount of water adsorbed, L 9
Amount of sorbent in one adsorber, kg 21
Output pressure, bar 2
Oil feeding height in relation to outlet fitting, m 20
Maximum power requirement, V, not more than 500
Electric Current Parameters  
Number of phases 3p+1N+PE
Voltage, V 380
AC with frequency, Hz 50
Attachment Dimensions  
Oil inlet, DN 20
Oil outlet, DN 20
Dimensions, not more than  
length, mm 1,180
width/width including a subframe, mm 350/550
height/height including a subframe, mm 2,035/2,085
Weight, kg, not more than 500
 
Advantages  
Benefits

More detail about Grid Vision T&D Sdn Bhd
Grid Vision T&D Sdn Bhd
Grid Vision T&D Sdn Bhd Remote Terminal Unit (RTU) Selangor, Transformer Monitoring System Supply Kuala Lumpur (KL), Power System Automation Supplier Malaysia ~ Grid Vision T&D Sdn Bhd
Contact Us flagMalaysia