RCD 010 THD is a room Carbon Dioxide (CO2) + Humidity (rH) + Temperature (T) transmitter with colored LCD display to show actual value of each parameter CO2+rH+T.
The combined Carbon Dioxide (CO2) + Humidity (rH) + Temperature (T) transmitter RCD 010 THD have 3 analogue outputs, i.e. one 0-10 Vdc output for each parameter CO2+rH+T.
Selectable ranges for Carbon Dioxide (CO2) + Humidity (rH) + Temperature (T)
with DIP switches on pcb.
The RCD 010 THD combined Carbon Dioxide (CO2) + Humidity (rH) + Temperature (T) transmitter to be used in air conditioning, ventilation and clean room technology, interior rooms such as residential rooms, offices, hotels, technical rooms, meeting rooms and convention centres.
RCD 010 THD combined Carbon Dioxide (CO2) + Humidity (rH) + Temperature (T) transmitter can be connected with DDC/PLC controller or other automation system such BAS, BMS, BEMS etc
Features
• Carbon Dioxide (CO2) output 0-10 Vdc
• Humidity (rH) output 0-10 Vdc
• Temperature (T) output 0-10 Vdc
• LCD display (colored)
• Carbon Dioxide (CO2) sensor
NDIR Sensor with auto calibration
• Carbon Dioxide (CO2) ranges
0-2000 ppm or 0-5000 ppm
• Carbon Dioxide (CO2) accuracy
±60 ppm for range 0-2000 ppm ± 2% f.s
±150 ppm for range 0-5000 ppm ± 2% f.s
• Temperature (T) accuracy
± 0.3°K (+5°C to +60°C) +2.5% f.s.
• Humidity (rH) accuracy
± 2% (20 to 80% rH) +2% f.s.
• DIP switch on pcb to select:
- Relative Humidity,
- Absolute Humidity,
- Dew Point or
- Enthalpy
• Passive temperature sensing element
PT1000, PT100, NTC 10K, NTC 20K, NTC 1.8K , NI1000 etc as option
• VOC sensor output on request
More detail about Excel Test Sdn Bhd