SBS-H2-DoD HYDROGEN GAS DETECTOR

SBS-H2-DoD HYDROGEN GAS DETECTOR

Category: Gas Detection Out of stock
For more information, visit our official website at lelab.com.my

Description

Hydrogen Sensor and Monitoring System


Benefits

Features

Installation

Detector can operate exhaust fans and building alarms / SCADA systems:

battery hydrogen sensor diagram

Warning Settings: Should the concentration of hydrogen gas in the air surrounding the sensor reach 0.5% by volume, the “0.5% Warning” yellow LED will light up on the main control of the unit. In addition, the 0.5% internal relay will energize and can be used to activate an external exhaust fan or a building management/alarm system (via SCADA Modbus).

Alarm Settings: Should the hydrogen gas concentration reach 1% by volume, the “1% Alarm” red LED will light up, the strobe will flash and an audible alarm will sound. In addition, the 1% internal relay will energize and can be used to activate a building management/alarm system (via SCADA/Modbus).

SBS-H2-DoD Includes

Specification

Power Supply(s) 110/220 Vac, 50/60 Hz and/or
12–48 Vdc (9–58 Vdc operating voltage)
12.5% LEL (Lower Explosive Limit) Dry contacts rated 10A/250 Vac
25% LEL (Lower Explosive Limit) Dry contacts rated .5A/28 Vdc
Dimensions 4.7'' L x 4.7'' W x 1.2'' D (main control)

More detail about LELab Sdn Bhd
LELab Sdn Bhd
LELab Sdn Bhd Laboratory Equipment Malaysia, Titrator & Sonicator Cleaning Bath | LELab Sdn Bhd
Contact Us flagMalaysia