VEGATRENN 151

Category: Vega Protective Separating Instruments Available
For more information, visit our official website at radartankgauging.com.my

Description

VEGATRENN 151

Separator for 4 … 20 mA sensors

Single channel , passive

Application area

The single channel VEGATRENN 151 is used for galvanic separation of intrinsically safe applications as well as signal transmission of Ex-approved 4 … 20 mA sensors in hazardous areas. The separator is ideal in conjunction with controllers without own Ex approval. The VEGATRENN 151 is suitable for bidirectional transmission of HART signals. The HART signal can be picked off via the HART communication sockets integrated in the front or the terminals. The complete HART permeability allows complete access to the sensor settings.
 

Your benefit

  • Simple installation because no additional voltage supple required
  • Simple installation though carrier rail mounting as well as detachable, coded terminals
  • Reliable separation of intrinsically safe and non-intrinsically safe measuring circuits (use in hazardous areas is optional)
Protection rating IP20
Input 1 x 4 … 20 mA/HART sensor input
Output 1 x 4 … 20 mA
Ambient temperature -20 ... 60 °C
Scope
-ATEX / Europe
-CSA / Canada
-EAC (GOST) / Belarus
-EAC (GOST) / Kazakhstan
-EAC (GOST) / Russia
-NEPSI / China
-UKR Sepro / Ukraine
SIL qualification SIL2

 