Rated power supply voltage |
24 to 240 VAC 50/60 Hz 24 to 240 VDC Ripple 20% max. |
---|---|
Allowable voltage variable range | 85 to 110% of the power supply voltage |
Power consumption | Approx. 4.5 VA (at 240 VAC) |
Reset voltage | 10% max. of rated supply voltage |
Number of time ranges | 8 |
Operation mode | ON delay, Flicker ON start, Interval, One shot output |
Control output (Type) | Time-limit: SPDT |
Control output (Contact output) |
Resistive load: 250 VAC 5 A (cosφ=1)/5 A at 30 VDC/0.5 A max. at 125 VDC Minimum applicable load: 10 mA at 5 VDC (failure level: P Reference value) |
Ambient temperature range |
Operating: -20 to 55 ℃ (with no icing) Storage: -40 to 70 ℃ (with no icing) |
Ambient humidity range | Operating: 25 to 85 % |
Accuracy of operating time | ±1% FS max. (±1% ±10 ms in a range of 1.2 s) |
Setting error | ±10% FS ±0.05 s max. |
Influence of voltage | ±0.5% FS max. (±0.5% ±10 ms in a range of 1.2 s) |
Influence of temperature | ±2% FS max. (±2% ±10 ms in a range of 1.2 s) |
Insulation resistance | 100 MΩ min. (at 500 VDC) |
Dielectric strength |
Between current carrying metal parts and non-current carrying metal parts: 2,000 VAC 50/60 Hz 1 min Between control output terminals and operating circuit: 2,000 VAC 50/60 Hz 1 min Between non-continuous contacts: 1,000 VAC 50/60 Hz 1 min |
Impulse withstand voltage |
Between power terminals: 5 kV Between current carrying terminals and exposed non-current carrying metal parts: 5 kV |
Noise immunity | ±1.5 kV square-wave noise by noise simulator (pulse width: 100 ns/1 µs, 1-ns rise) |
Static immunity | Mulfunction: 4 kV, Destruction: 8 kV |
Vibration resistance |
Destruction: 10 to 55 Hz, 0.75 mm single amplitude each in 3 directions for 2 h Malfunction: 10 to 55 Hz, 0.5 mm single amplitude each in 3 directions for 10 min |
Shock resistance |
Destruction: 1,000 m/s2, 3 times each in 6 directions Malfunction: 100 m/s2, 3 times each in 6 directions |
Life expectancy (relay output) |
Electrical: 100,000 operations min. (5 A at 250 VAC, resistive load at 360 operations/h) Mechanical: 10 million operations min. (under no load at 1,800 operations/h) |
Degree of protection | IP30 (Terminal Block: IP20) |
Connecting method | Terminal blocks |
Weight | Approx. 120 g |
Accessories | User label |