KEY FEATURES:
HIGH YIELD
SG110CX-P2-CN Inverter Specifications | |
---|---|
Type designation | SG110CX-P2-CN |
Input (DC) | |
Max. PV input voltage | 1100V |
Min. operating PV voltage / Start-up input voltage | 180V / 200V |
Rated PV input voltage | 640V |
MPPT voltage range | 180~1000V |
No. of independent MPP inputs | 9 |
No. of PV strings per MPPT | 2 |
Max. PV input current per String | 15A |
Max. PV input current | 270A (9×30A) |
Max. PV input current per Input Connector | 30A |
Max. DC short-circuit current | 360A (9×40A) |
Output (AC) | |
Rated AC output power | 110kW |
Max. AC output power | 121kW |
Max. AC output apparent power | 121kVA |
Max. AC output current | 183.3A |
Rated AC voltage | 3 / N / PE, 230/400V |
AC voltage range | 320~480V |
Rated grid frequency / Grid frequency range | 50Hz / 45~55Hz 60Hz / 55~65Hz |
Harmonic (THD) | < 3% (at rated power) |
Power factor at nominal power | > 0.99 (at rated power) |
Adjustable power factor | 0.8 leading – 0.8 lagging |
Feed-in phases / AC connection | 3 / 3 |
Efficiency | |
Max. efficiency | 98.60% |
European efficiency | 98.00% |
Protection and Function | |
DC reverse polarity protection | Yes |
AC short-circuit protection | Yes |
Leakage current protection | Yes |
Grid monitoring | Yes |
DC switch | Yes |
PV string monitoring | Yes |
Anti-Islanding protection | Yes |
Surge protection | DC Type II / AC Type II |
General Data | |
Dimensions (W*H*D) | 1019*793*360mm |
Weight | 82kg |
Topology | Transformerless |
Degree of protection | IP66 |
Night power consumption | ≤ 4W |
Operating ambient temperature range | -30~+60℃ |
Allowable relative humidity range | 0~100% |
Cooling method | Smart forced air cooling |
Max. operating altitude | 4000m (>3000m derating) |
Display | LED, Bluetooth+APP |
Communication | RS485 / Optional: WLAN, Ethernet |
DC connection type | MC4 |
AC connection type | OT / DT terminal (From 70 ~ 240 mm²) |
Compliance with Standard | NB/T 32004-2018; GB/T 37408-2019 |
Grid Support | LVRT, HVRT, Anti-Islanding, active & reactive power control, and power ramp rate control |