Network frequency |
0...400 Hz |
Mounting support |
Plate, with specific accessories
Rail, with specific accessories
Under contactor |
Tripping threshold |
1.14 +/- 0.06 Ir conforming to IEC 60947-4-1 |
Auxiliary contact composition |
1 NO + 1 NC |
[Ith] conventional free air thermal current |
5 A for signalling circuit |
Permissible current |
0.06 A at 440 V DC-13 for signalling circuit
0.12 A at 600 V AC-15 for signalling circuit |
[Ue] rated operational voltage |
1000 V AC 0...400 Hz for power circuit conforming to IEC 60947-4-1 |
Associated fuse rating |
4 A gG for signalling circuit
4 A BS for signalling circuit |
[Uimp] rated impulse withstand voltage |
6 kV conforming to IEC 60947-1 |
Phase failure sensitivity |
Tripping current 130 % of Ir on two phase, the last one at 0 |
Control type |
Red push-button: stop
Blue push-button: reset |
Temperature compensation |
-20…60 °C |
Connections - terminals |
Power circuit: screw clamp terminals 1 cable(s) 4…35 mm² flexible with cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² flexible with cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² solid without cable end
Power circuit: screw clamp terminals 1 cable(s) 4…50 mm² flexible without cable end
Power circuit: screw clamp terminals 1 cable(s) 4…50 mm² solid without cable end |
Tightening torque |
Control circuit: 1.7 N.m - on screw clamp terminals
Power circuit: 9 N.m - on screw clamp terminals |
Depth |
132 mm |
Net weight |
0.9 kg |