Power supply
Supply voltage : 85..253 V AC / 110..125 V DC or
10..30 V AC/DC
Frequency AC : 40..400 Hz
Power consumption : < 3.5 VA
Operating
temperature : -10..+55 °C
CE-conformity : ATEX-directive 2014/34/EU
Standards : EN 60079-0:2006, EN 60079-11:2007
EN 60079-25:2004
EN 61241-0:2006, EN 61241-11:2006
EMC-directive : 2014/30/EU / EN 61326-1:2013
Inputs
Current : 0/4..20 mA DC, selectable, Ri = 25 Ω,
overload max. 100 mA
Voltage : 0/2..10 V DC, selectable, Ri ca. 40 kΩ,
overload max. 100 V
Span : adjustable approx. ± 5 %
Zero point : adjustable approx. ± 5 %
Explosion protection
Certification : TÜV 97 ATEX 1164
Approval : II (1) G [Ex ia Ga] IIC or
II (1) D [Ex ia Da] IIIC
Outputs
Current : 0/4..20 mA DC, selectable
burden ≤ 320 Ω (TV501Ex-..-10)
burden ≤ 1 kΩ (TV501Ex-..-20)
Voltage : 0/2..10 V DC, selectable,
max. 15 mA short-circuit-proof,
(parallel with voltage output max. 5 mA)
Rise time (T90) : < 20 ms
Accuracy : ≤ 0.3 %
Case : standard case polycarbonate 8020 UL94V-1
DIN rail mounting TS35
Weight : approx. 200 g
Electrical
connection : screw terminals, max. 2.5 mm²
Protection class : case IP30, terminals IP20 acc. to BGV A3